Jun 23, 2023
Permit/Opening
5 - emergency phone operational and accessible
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Observed the emergency phone wires exposed and not working. RCA: An operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all times. The emergency phone shall be capable of connecting to 911 and electronically transferring an automatic number identification and automatic locator identification of the pool emergency phone to the public safety answering point, if available. A 911 sign or the names and phone numbers of the nearest available police, fire, ambulance service or rescue unit shall be posted nearby.
6 - proper disinfectant level
Regulation: .17((1)(c) - proper disinfectant level
Observed disinfectant level of 0.53ppm. RCA: Chlorine disinfectant level must be between 2ppm-10ppm.
11 - appropriate lifesaving equipment present
Regulation: 511-3-5-.18(10)(a) - (a) a light, strong pole not less than twelve feet long including body hook.
Observed no strong pole including a body hook. RCA: A light, strong pole not less than twelve feet long including body hook shall be provided.
28 - flow meter: appropriate range and location
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter not working. RCA: A flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided. The flow indicator shall be capable of measuring from one-half to at least one and one-half times the design flow rate. The gauge shall be located after the filtering equipment and in such location on the return line, so as to measure the total amount of water returning to the pool according to the manufacturer’s installation specifications.
30 - deck/rinse shower maintained
Regulation: 511-3-5-.18(17) - (17) a minimum of one rinse shower shall be provided on the pool deck of all public pools and spas. water used for rinse showers may be at ambient temperature.
Observed no nozzle on the rinse shower to turn the water on. RCA: A minimum of one rinse shower shall be provided on the pool deck of all public pools and spas. Water used for rinse showers may be at ambient temperature.
37 - other violations of the chapter
Observed Calcium Hardness level at 119. RCA: CH shall meet a minimum of 150.