May 21, 2026
Re-inspection
600 WATERSTONE DR CANTON, GA 30114
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Re-inspection
Permit/Opening
Regulation: .17((1)(c) - proper disinfectant level
Observed chlorine greater than 10ppm. Must be between 2 and 10ppm.
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
Observed pH less than 7.0. Must be between 7.2 and 7.8. 511-3-5-.17(2) - (2) Chemical Values: pH (2) Chemical Values: pH 7.2 7.4-7.6 7.8 Alkalinity (buffering), 60 ppm 80-100 halogens compounds with high pH 180 ppm as CaC03 100-120 halogen compounds with low pH Calcium hardness, ppm, CaCo3 150 200-400 to balance water 1000
Regulation: 511-3-5-.07(4)(a) - (a) a pressure or vacuum gauge or other means of indicating system condition shall be provided in the circulation system in an easily readable location.
Must provide effluent pressure gauge on the return line.
Regulation: 511-3-5-.18(12)(c) - (c) the same sign in subsection (b) above or an additional sign will state under the heading “pool risks” the following items in clearly legible letters at least one inch high:
Must post the pool risks sign.
Re-inspection
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Unable to observe turnover rate due to flow meter not working. Must fix flow meter.
Re-inspection
Regulation: .17((1)(c) - proper disinfectant level
Observed a Cl- of 14 ppm. Must be between 2-10 ppm.
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Unable to observe turnover rate due to flow meter not working. Must fix flow meter.
Routine
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
Observed a pH well above 8.0. The pH must be between 7.2-7.8.
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Unable to observe turnover rate due to flow meter not working. Must fix flow meter.
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed handrail near pump room in disrepair. Must fix asap.
Permit/Opening
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Hand rail is fairly loose. Must tighten prior to opening for season.
Re-inspection
Re-inspection
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
Observed a pH of 7.0. pH must be between 7.2-7.8.
Routine
Regulation: .17((1)(c) - proper disinfectant level
Observed 0 ppm Cl-. Free Cl- levels must be between 2.0-10 ppm. COS by adding Cl- to chemical feeder.
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed a turnover rate of 110 gpm. The required turnover rate for this pool is 124 gpm. CPO plans to change filters. Health authority recommended back washing as well.
Permit/Opening
Regulation: 511-3-5-.10(7) - (7) the vacuum line shall be protected with a self-closing, self-latching fitting that complies with the current iampo sps 4- special use suction fitting for swimming pools, spas and hot tubs.
The vacuum line shall be protected with a spring loaded, self-closing, self-latching fitting that complies with the current IAMPO SPS 4- Special Use Suction Fitting for Swimming Pools, Spas and Hot Tubs.
Regulation: 511-3-5-.07(4)(a) - (a) a pressure or vacuum gauge or other means of indicating system condition shall be provided in the circulation system in an easily readable location.
A pressure or vacuum gauge or other means of indicating system condition shall be provided in the circulation system in an easily readable location.
Regulation: 511-3-5-.18(12)(b) - (b) where no lifeguard is on duty, a sign or signs shall be placed in clear view at or near the entrance to the pool and shall state in clearly legible letters at least four inches high “warning - no life guard on duty and risk of drowning - supervis
A sign or signs shall be placed in clear view at or near the entrance to the pool and shall state in clearly legible letters at least four inches high “WARNING - NO LIFE GUARD ON DUTY and RISK OF DROWNING - SUPERVISE CHILDREN CLOSELY”.
Routine
Re-inspection
Permit/Opening
Regulation: .17(1)(a)(b) - proper disinfectant level
Chlorine at 18ppm. Must be below 10ppm.
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
pH is less than 7.0. Must be between 7.2 and 7.8
Regulation: 511-3-5-.22(2) - (2) the trained operator shall have a current certificate showing completion of an approved operator training course. a copy or the original certificate or documentation shall be available onsite for inspection by the health authority.
Must post a copy of the CPO certificate.
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Must tighten the hand rail. Must replace the eustecheon plate
Facility has an expired test kit. Must be able to check all the chemistry.