Aug 23, 2024
Routine
6 - proper disinfectant level
Regulation: .17((1)(c) - proper disinfectant level
Chlorine was 0.5ppm or below at the beginning of inspection. Chlorine levels must be between 2.0 - 10.0ppm (.17((1)(c))
7 - ph between 7.2 and 7.8
pH levels were below 7.0 at the time of inspection. pH levels must be between 7.2 - 7.8 (511-3-5-.17(2))
28 - flow meter: appropriate range and location
Flow rate was 100 GPM at time of inspection, Flow rate must be to 120 GPM or greater to achieve required turnover rate.
21 - cyanuric acid level not exceeding maximum
Observed cyanuric acid exceeding maximum. Must be below 90 ppm.