Holly Springs, Cherokee County

Oakhaven

201 WALNUT RIDGE RD CANTON, GA 30115

Pool
Latest score
100
Apr 22, 2026
City
Holly Springs
County
Cherokee
Inspections
6

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Apr 22, 2026

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Aug 1, 2025

Routine

Score: 961 violation

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

Cyanuric acid is >100 ppm. Reduce to below 90 (Ideal 30-50)

Mar 26, 2025

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Jul 11, 2024

Routine

Score: 932 violations

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(9) - (9) water testing frequency. the trained operator or responsible person shall collect water samples from the water in the pool for monitoring. an in-line sampling port may be used for water held in reservoirs. the water quality testing frequency shal

5 ptsCorrected: NoRepeat: No

No onsite daily logs for chemical testing - Trained operator/HOA/Property Management shall test the pools twice daily for pH and free Chlorine, weekly for alkalinity, monthly for hardness, and twice monthly for cyanuric acid.

12 - grab/hand rails, ladders installed and secure

Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.

2 ptsCorrected: NoRepeat: No

Handrail on far end of pool not secure - repair

511-3-5-.06(3)(f)1. - 1. Handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.

  1. Handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.

Mar 27, 2024

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Jul 23, 2023

Routine

Score: 883 violations

17 - skimmers/gutters maintained and operable

4 ptsCorrected: NoRepeat: No

Skimmer baskets must be emptied--they are full of leaves and more.

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

Cyanuric acid is >90 ppm. Must be below 90.

32 - operator training certification available onsite and approved

Regulation: 511-3-5-.22(2) - (2) the trained operator shall have a current certificate showing completion of an approved operator training course. a copy or the original certificate or documentation shall be available onsite for inspection by the health authority.

4 ptsCorrected: NoRepeat: No

There is no CPO certificate in pump room.