Mar 24, 2026
Permit/Opening
306 HERRINGTON CT WOODSTOCK, GA 30188
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Flow Meter was stuck at time of inspection - Repair
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
Cyanuric Acid is greater than 100 ppm - Maintain below 90 ppm
511-3-5-.17(4) - (4) Stabilizer (if used) Cyanuric acid,ppm Ideal: 30-50 Maximum: 90 Comments: If stabilizer is: Too High: - May reduce chlorine efficacy Too Low: - Chlorine Residual rapidly destroyed by sunlight Note: Stabilizer is not needed in indoor or br (4) Stabilizer (if used) Cyanuric acid,ppm Ideal: 30-50 Maximum: 90 Comments: If stabilizer is: Too High: - May reduce chlorine efficacy Too Low: - Chlorine Residual rapidly destroyed by sunlight Note: Stabilizer is not needed in indoor or brominated pools and spas.
Permit/Opening
Routine
Flow meter was reading 225 GPM - Increase flow rate to at least 270 GPM to achieve 6hr turnover rate.
No daily pool testing records onsite (Only CPO's twice weekly logs) - Test pool twice daily for Chlorine and pH, Weekly for alkalinity, monthly for hardness and twice monthly for cyanuric acid.
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
Cyanuric Acid is greater than 100 ppm - Maintain below 90 ppm
511-3-5-.17(4) - (4) Stabilizer (if used) Cyanuric acid,ppm Ideal: 30-50 Maximum: 90 Comments: If stabilizer is: Too High: - May reduce chlorine efficacy Too Low: - Chlorine Residual rapidly destroyed by sunlight Note: Stabilizer is not needed in indoor or br (4) Stabilizer (if used) Cyanuric acid,ppm Ideal: 30-50 Maximum: 90 Comments: If stabilizer is: Too High: - May reduce chlorine efficacy Too Low: - Chlorine Residual rapidly destroyed by sunlight Note: Stabilizer is not needed in indoor or brominated pools and spas.
Permit/Opening
Routine
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
Cyanuric acid is greater than 100ppm.