Permit/Opening
Routine
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Flow meter not functioning - repair/replace flow meter
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
CYA is greater than 100. Ideal 30-50 with a Maximum of 90.
511-3-5-.17(4) - (4) Stabilizer (if used) Cyanuric acid ppm Ideal: 30-50 Maximum: 90 Comments: If stabilizer is: Too High: - May reduce chlorine efficacy Too Low: - Chlorine Residual rapidly destroyed by sunlight Note: Stabilizer is not needed in indoor or brominated pools or spas
Fountain was not operational at time of inspection - Repair drinking fountain
511-3-5-.18(16) Specific Safety Features and Markers. (16) At least one drinking fountain shall be provided and available to users at the pool site.
No diaper changing stations - Install diaper changing stations in both mens and womens restrooms.
511-3-5-.19 Dressing Facilities and Sanitary Facilities. (m) Facilities shall provide a minimum of one diaper changing station in the male and female bathroom or dressing area
Permit/Opening
Routine
Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Flow meter reading 150 GPM (Very difficult to read) - Replace flow meter and ensure flow of 240 gal per minute to meet turnover requirments.
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
CYA is greater than 100. Ideal 30-50 with a Maximum of 90.
Regulation: 511-3-5-.18(12)(c) - (c) the same sign in subsection (b) above or an additional sign will state under the heading “pool risks” the following items in clearly legible letters at least one inch high:
No pool risks sign present - Post updated "Pool Risks" sign.
No diaper changing stations - Install diaper changing stations in both mens and womens restrooms
Permit/Opening
Regulation: 511-3-5-.18(12)(c) - (c) the same sign in subsection (b) above or an additional sign will state under the heading “pool risks” the following items in clearly legible letters at least one inch high:
Must post "Pool Risks" sign
Routine
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
CYA is greater than 100. Ideal 30-50 with a Maximum of 90. Must lower.
Permit/Opening