Jun 10, 2025
Re-inspection
1200 LAKE RIDGE PKWY RIVERDALE, GA 30296
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Re-inspection
Routine
Regulation: 511-3-5-.10(7) - (7) the vacuum line shall be protected with a self-closing, self-latching fitting that complies with the current iampo sps 4- special use suction fitting for swimming pools, spas and hot tubs.
Observed one dedicated vacuum port without self closing/latching cover. CA: All dedicated vacuums shall have self closing/latching cover.
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter stuck. Could not ascertain if pool was getting required 6 hour turnover rate or better. Advised to repair and advised flow meter must measure at least 224 GPM.
Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.
Observed no daily self inspections at facility. CA: Daily required safety self checks shall be made and documentation kept at facility.
Regulation: 511-3-5-.22(9) - (9) water testing frequency. the trained operator or responsible person shall collect water samples from the water in the pool for monitoring. an in-line sampling port may be used for water held in reservoirs. the water quality testing frequency shal
Observed no records of pH and chlorine being tested daily. CA:A trained operator or responsible person shall take pH and chlorine minimum 2 times daily and log.
Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
Observed several missing weirs. COS: PIC placed weirs in skimmers. CA: All skimmers shall have working weirs.
Regulation: 511-3-5-.18(13)(b) - (b) warning signs for spas shall be in clear view of the spa and prominently displayed. signs shall state the spa's address, the location of the nearest telephone with references that emergency telephone numbers are posted at the location. these emer
Observed no 911 sign at emergency phone and no street address posted for pool. COS: PIC placed 911 sign on phone box and posted address on phone box.
Permit/Opening
Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Observed turnover rate greater than 6-hours. Advised PIC equipment shall be able turn volume in required time.
Regulation: 511-3-5-.18(12)(b) - (b) where no lifeguard is on duty, a sign or signs shall be placed in clear view at or near the entrance to the pool and shall state in clearly legible letters at least four inches high “warning - no life guard on duty and risk of drowning - supervis
Observed No 'No lifeguard on duty: supervise children closely' signage at pool. Advised PIC 'No lifeguard on duty: supervise children closely signage.
Regulation: 511-3-5-.08(6) - (6) all piping shall be marked with directional arrows as necessary to determine flow direction. all piping in the equipment room shall be permanently identified by its use and the pool and or aquatic feature it serves.
Observed no marking direction of flow on piping. Advised PIC direction of flow shall be marked.
Re-inspection
Regulation: 511-3-5-.06(1)(f) - (f) the deck, including coping, shall have a minimum four feet width of continuous, unobstructed walking area maintained at all times unless otherwise allowed in the chapter.
Observed multiple cacks on pool deck area. Advised CPO/PIC that the pool deck shall be unobstructed. Also advised CPO/PIC to resurface pool deck at the end of 2023 pool season.
Regulation: 511-3-5-.18(13)(c) - (c) a sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.
Observed "pool capacity" signage with no written capacity number. Advised CPO/PIC that a pool occupancy sign shall be placed near the entrance and inside deck area.
Permit/Opening
Regulation: 511-3-5-.07(1)(e ) - (e) water clarity shall be maintained. when standing at the pool's edge at the deep end, the main drain suction outlet covers or a four inch by four inch square marker tile in contrasting color shall be clearly visible. when standing at a spa's e
Upon arrival, observed poor water clarity and main drain covers not visibly clear. Advised CPO/PIC that main drain covers are clearly visible when standing at the deep end of pool edge.
Regulation: 511-3-5-.06(1)(f) - (f) the deck, including coping, shall have a minimum four feet width of continuous, unobstructed walking area maintained at all times unless otherwise allowed in the chapter.
Observed multiple cracks on pool deck. Advised CPO/PIC to resurface pool deck at the end of pool season.
Regulation: 511-3-5-.18(13)(c) - (c) a sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.
Observed "pool capacity" signage with no written capacity number. Advised CPO/PIC to place a pool occupancy sign near entrance and pool deck.