Apr 29, 2026
Permit/Opening
4791 WINDRUSH LN NW ACWORTH, GA 30102
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
Permit/Opening
Routine
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed float device stuck in flow meter.
CA: Replace or fix flow meter.
Routine
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
clean or replace flow meter
Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
skimmers missing weirs
Re-inspection
Routine
Chlorine is at 14ppm. Chlorine shall be between 2-10ppm
Re-inspection
Routine
Regulation: .17((1)(c) - proper disinfectant level
Chlorine observed at 17 ppm.