KENNESAW, Cobb County

COMFORT INN KENNESAW - TOUR

2489 GEORGE BUSBEE PKWY NW KENNESAW, GA 30144-4961

Tourist
Latest score
83
Feb 23, 2026
City
KENNESAW
County
Cobb
Inspections
5

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Feb 23, 2026

Routine

Score: 836 violations

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: Yes

Facility unable to provide gas-fired equipment inspection during time of inspection.

C/A: Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency.

PIC shall provide proof of gas-fired equipment inspection to EHS (zyier.wilcher@dph.ga.gov) via email by 3/2/2026

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: No
  1. Observed black buildup on AC unit in room 419.
  2. Observed inoperable light bulbs in rooms 510 and 414.

C/A: All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

Observed stains on pillows, comforter, mattress and/or sheets in rooms 419, 510, and 517.

C/A: Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin

10 - permit and inspection report current and properly displayed; pic assigned

Regulation: 511-6-2-.05(7) - inspection posting

2 ptsCorrected: NoRepeat: No

Most recent tourist accommodation inspection report (8/4/2025) was not posted.

C/A: The most recent tourist accommodation inspection report form shall be prominently displayed in public view at all times, between five feet and seven feet from the floor and in a public area such as the registration desk, where it can be read at a distance of one foot away

15 - ice from approved source; properly handled, supplied and stored; equipment approved/clean

Regulation: 511-6-2-.07(8) - ice supply

1 ptsCorrected: NoRepeat: Yes

Observed pink buildup on ice chute on 1st and 5th floor.

C/A: Ice machines shall be maintained cleaned and sanitized

33 - housekeeping carts and storage areas maintained; clean/sanitized items protected from contamination

Regulation: 511-6-2-.17(2) - housekeeping carts

1 ptsCorrected: NoRepeat: No

Observed unlabeled chemicals on 5th floor housekeeping cart and in housekeeping laundry room.

C/A: Any spray bottle used in cleaning a tourist room or stored on the housekeeping cart shall be labeled with its contents

Aug 4, 2025

Routine

Score: 893 violations

3 - hot/cold running water under pressure in all required locations of tourist accommodation

Regulation: 511-6-2-.07(2) - hot water supply

5 ptsCorrected: NoRepeat: No

Observed hot water in all rooms entered during inspections above 120F: 523, 514, 419, 318, and 215.

C/A: hot water in all guest rooms shall not exceed 120F.

POC: lower water heater temperature and have water below 120F by Friday, August 8th

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: Yes

Facility unable to provide gas-fired inspection and facility unable to provide proof that the annual gas-fired inspection has been scheduled/conducted.

C/A: All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency

POC: Facility is to email EHS a copy of the gas-fired inspection report by Friday, August 8th, 2025. Failure to do so may result in disciplinary actions

15 - ice from approved source; properly handled, supplied and stored; equipment approved/clean

Regulation: 511-6-2-.07(8) - ice supply

1 ptsCorrected: NoRepeat: No

Observed pink slime on chute of the ice machine on the 5th floor.

C/A: In existing tourist accommodations permitted prior to the adoption of this rule, the use of existing self-service ice-storage bins may be continued, provided that the machines are maintained in good repair and capable of being properly cleaned and sanitized according to the manufacturer’s recommendations

Jan 16, 2025

Routine

Score: 932 violations

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: Yes

Last gas-fired inspection report conducted 1/2/24, and facility unable to provide proof that the annual gas-fired inspection has been scheduled/conducted.

C/A: All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency

POC: Facility is to email EHS a copy of the gas-fired inspection report by Thursday, January 23, 2025

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: Yes

Observed inoperable ventilation in the bathrooms of rooms 510, 423, 417, 312, 217, and 122. Observed an odor in room 510.

C/A:Toilet, lavatory and bathing facilities shall be mechanically ventilated. Where ventilation ducts are used, ducts from toilet rooms shall not be connected into return ventilation ducts to any other room. In existing tourist accommodations permitted prior to the adoption of this rule, the current ventilation must prevent odor, mold, mildew, and moisture. All new or major renovation of a tourist accommodation will require mechanical ventilation to be installed to the outside of the building separate from heating and air-condition systems

May 31, 2024

Routine

Score: 835 violations

3 - hot/cold running water under pressure in all required locations of tourist accommodation

Regulation: 511-6-2-.07(2) - hot water supply

5 ptsCorrected: NoRepeat: Yes

Observed hot water exceeding 120F in rooms 514, 310, 212, and 111.

C/A: In all new tourist accommodations, and where possible in existing tourist accommodations, hot water in all guest rooms shall not exceed 120F

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: Yes

Facility unable to provide last annual gas fired inspection upon request of health authority.

C/A: All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency

Please send gas-fired inspection to EHS within 10- calendar days to conform to compliance; business card provided.

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

Observed stained mattress cover in room 522. Observed stained mattress in room 310 and 212.

C/A: Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: Yes

Observed inoperable ventilation in restroom of rooms 522, 514, 416, 310, 212, and 111.

C/A: Repair ventilation; Toilet, lavatory and bathing facilities shall be mechanically ventilated. Where ventilation ducts are used, ducts from toilet rooms shall not be connected into return ventilation ducts to any other room. In existing tourist accommodations permitted prior to the adoption of this rule, the current ventilation must prevent odor, mold, mildew, and moisture

15 - ice from approved source; properly handled, supplied and stored; equipment approved/clean

Regulation: 511-6-2-.07(8) - ice supply

1 ptsCorrected: NoRepeat: Yes

Observed pink and black substance along interior spout of ice machines on floors 1 and 3.

C/A: Clean/sanitize machines; ice machines shall be stored in a clean place and shall be kept clean

EHS will return with-in 10 calendar days to check on the status of the ice machines on the 1st and 3rd floor

Dec 12, 2023

Routine

Score: 874 violations

3 - hot/cold running water under pressure in all required locations of tourist accommodation

Regulation: 511-6-2-.07(2) - hot water supply

5 ptsCorrected: NoRepeat: No

Observed hot water exceeding 120F in rooms 410, 412, and 113.

C/A: In all new tourist accommodations, and where possible in existing tourist accommodations, hot water in all guest rooms shall not exceed 120F.

COS: Staff lowered hot water heater thermostat

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: No

Facility unable to provide last annual gas fired inspection upon request of health authority.

C/A: All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency

Please send gas-fired inspection to EHS within 10-days to conform to compliance; business card provided.

Informal-12/22/23- Deadline extended to 1/5/2024 at request of facility due to facility owner being ill.

COS-Informal-1/9/2024: PIC provided annual gas fired inspection documentation to EHS; gas fired inspection conducted 1/2/2024

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: No

Observed inoperable ventilation in restroom of rooms 410, 412, and 113.

C/A: Repair ventilation; Toilet, lavatory and bathing facilities shall be mechanically ventilated. Where ventilation ducts are used, ducts from toilet rooms shall not be connected into return ventilation ducts to any other room. In existing tourist accommodations permitted prior to the adoption of this rule, the current ventilation must prevent odor, mold, mildew, and moisture

15 - ice from approved source; properly handled, supplied and stored; equipment approved/clean

Regulation: 511-6-2-.07(8) - ice supply

1 ptsCorrected: NoRepeat: No

Observed pink and black substance along interior spout of ice machines on floors 1 and 3.

C/A: Clean/sanitize machines; ice machines shall be stored in a clean place and shall be kept clean