Permit/Opening
2151 DRESDEN GREEN KENNESAW, GA 30144
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Float device missing from flow meter.
CA: Replace flow meter.
Permit/Opening
Regulation: 511-3-5-.19(2)(i) - (i) soap, paper towels, and toilet tissue shall be provided in all dispensers.
Bathrooms dirty and not stocked with paper towels, soap, and toilet paper.
CA: Clean bathrooms and stock everything.
Regulation: 511-3-5-.19(1)(b) - (b) dressing facilities, when provided, shall be have separations for each sex with no interconnection. the rooms shall be well-lighted, drained, ventilated, and of good construction with impervious materials. they shall be developed and planned so t
Shower not operating.
Replace shower head or repair.
Routine
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Flow meter observed at 0 ppm. Float device may be stuck. Replace or fix flow meter.
Lights in pump area need to be replaced.
Permit/Opening
Regulation: 511-3-5-.10(7) - (7) the vacuum line shall be protected with a self-closing, self-latching fitting that complies with the current iampo sps 4- special use suction fitting for swimming pools, spas and hot tubs.
Need compliant cover on the vacuum line (temp cap installed)
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Unclog or replace flow meter.
Need dual check on inline fill. Lights not operational in bathroom.
Routine
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed grab rails loose. CA: Tighten loose grab rails
Could not access pump room; could not find lockbox