KENNESAW, Cobb County

HICKORY SPRINGS HOA - POOL

910 THOUSAND OAKS BND KENNESAW, GA 30152

Pool
Latest score
95
May 12, 2026
City
KENNESAW
County
Cobb
Inspections
6

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

May 12, 2026

Permit/Opening

Score: 951 violation

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

Observed inoperable flowmeter. C/A: Repair/replace flowmeter.

Jul 21, 2025

Routine

Score: 981 violation

12 - grab/hand rails, ladders installed and secure

2 ptsCorrected: NoRepeat: No

observed all grab rails as loose. CA: Fix/ Tighten

Apr 29, 2025

Permit/Opening

Score: 982 violations

31 - dressing showers: clean, maintained, hot and cold water available

Regulation: 511-3-5-.19(1)(b) - (b) dressing facilities, when provided, shall be have separations for each sex with no interconnection. the rooms shall be well-lighted, drained, ventilated, and of good construction with impervious materials. they shall be developed and planned so t

1 ptsCorrected: NoRepeat: No

Observed shower in women's restroom inoperable. C/A: Ensure shower is operational.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

Observed no backflow prevention provided on pool deck hose taps(2). C/A: Install backflow prevention on hose tap used to fill pool.

Jul 26, 2024

Re-inspection

Score: 961 violation

17 - skimmers/gutters maintained and operable

4 ptsCorrected: NoRepeat: Yes

skimmers missing weirs

Jul 25, 2024

Routine

Score: 763 violations

6 - proper disinfectant level

Regulation: 511-3-5-.23(5)(a) - (a) during operation, disinfectant levels are less than the minimum level specified in dph rule 511-3-5-.17. if the level of the disinfectant used is not specified in dph rule 511-3-5-.17, the disinfectant must be approved and kept at levels determin

15 ptsCorrected: NoRepeat: No

chlorine observed at 12.5 ppm, maintain between 2-10ppm. Correct immediately. CPO was contacted and agreed to send technician out.

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

clean or replace flow meter

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: No

skimmers missing weirs

May 17, 2024

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.