KENNESAW, Cobb County

MAA SHILOH - BACK

1750 SHILOH RD NW KENNESAW, GA 30144

Pool
Latest score
100
May 21, 2026
City
KENNESAW
County
Cobb
Inspections
9

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

May 21, 2026

Re-inspection

Score: 1000 violations
No violations recorded for this inspection.

May 20, 2026

Permit/Opening

Score: 852 violations

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: No

Chlorine tested at 25ppm.

CA: Chlorine shall be maintained between 2-10ppm.

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.17(2) - (2) chemical values: ph

15 ptsCorrected: NoRepeat: No

pH observed above 8.0ppm.

CA: pH shall be maintained between 7.2 and 7.8ppm.

Jul 31, 2025

Routine

Score: 1000 violations
No violations recorded for this inspection.

May 13, 2025

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Aug 20, 2024

Routine

Score: 1000 violations
No violations recorded for this inspection.

May 9, 2024

Routine

Score: 1000 violations
No violations recorded for this inspection.

Aug 18, 2023

Routine

Score: 903 violations

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: Yes

No float device in flow meter, CA: needs to be replaced

26 - gauge(s) in proper location; sight glass installed

Regulation: 511-3-5-.08(5) - (5) a sight glass shall be installed on the waste discharge line of pressure filters so that the progress of filter washing can be observed.

4 ptsCorrected: NoRepeat: Yes

Observed no sight glass on pump; CA: Install sight glass on pump

29 - toilets & lavatories: clean, maintained, and stocked

Regulation: 511-3-5-.19(2)(n) - (n) sanitary facility fixtures and dressing area fixtures and furniture shall be cleaned and sanitized with an epa-approved product and as needed to provide a clean and sanitary environment.

1 ptsCorrected: NoRepeat: No

Observed leak under men's urinal; CA: Leaks needs to be fixtured

May 25, 2023

Re-inspection

Score: 912 violations

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

Flow meter observed below appropriate range. Float device needs to be replaced.

26 - gauge(s) in proper location; sight glass installed

Regulation: 511-3-5-.08(5) - (5) a sight glass shall be installed on the waste discharge line of pressure filters so that the progress of filter washing can be observed.

4 ptsCorrected: NoRepeat: No

No sight glass observed. Sight glass should be installed to view pressure in pump system.

May 24, 2023

Routine

Score: 763 violations

6 - proper disinfectant level

Regulation: .17((1)(c) - proper disinfectant level

15 ptsCorrected: NoRepeat: No

Chlorine level was observed above 20 ppm. The chlorine level needs to be between 3 and 10 ppm.

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

Flow meter was observed under the appropriate level. Float device needs to be replaced.

26 - gauge(s) in proper location; sight glass installed

Regulation: 511-3-5-.08(5) - (5) a sight glass shall be installed on the waste discharge line of pressure filters so that the progress of filter washing can be observed.

4 ptsCorrected: NoRepeat: No

Sight glass was not installed when pump was replaced. Sight glass should be installed to observe pressure in pump system.