Jun 5, 2026
Re-inspection
1810 ASHBOROUGH CIR SE MARIETTA, GA 30067-8910
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Re-inspection
Routine
Gate not self-latching. Uses a doorknob instead of typical gate latch. At time of inspection, it was purposely left open by swimmers because when closed, it was unable to be reopened.
Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.
pH observed at 7.0; too low (7.2-7.8 ideal range)
Permit/Opening
Permit/Opening
Regulation: .17((1)(c) - proper disinfectant level
chlorine observed at 17ppm, maintain between 2-10ppm
Permit/Opening
Regulation: 511-3-5-.18(10)(b) - (b) a minimum one-fourth inch diameter throwing rope one and one-half times the maximum width of the pool or fifty feet in length, whichever is less, to which has been firmly attached a ring buoy with an outside diameter of approximately fifteen inch
Observed throwing rope for life ring not the minimum length required
C/A/: A minimum one-fourth inch diameter throwing rope one and one-half times the maximum width of the pool or fifty feet in length, whichever is less, to which has been firmly attached a ring buoy with an outside diameter of approximately fifteen inches or a similar flotation device which is U.S. Coast Guard approved.
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed float stuck in flow meter; unable to determine flow rate
C/A: flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided. The flow indicator shall be capable of measuring from one-half to at least one and one-half times the design flow rate. The gauge shall be located after the filtering equipment and in such location on the return line, so as to measure the total amount of water returning to the pool according to the manufacturer’s installation specifications.
Regulation: 511-3-5-.18(12)(b) - (b) where no lifeguard is on duty, a sign or signs shall be placed in clear view at or near the entrance to the pool and shall state in clearly legible letters at least four inches high “warning - no life guard on duty and risk of drowning - supervis
Facility has changed signage; observed new signage not a minimum height requirement for lifeguard signage
C/A: Where no lifeguard is on duty, a sign or signs shall be placed in clear view at or near the entrance to the pool and shall state in clearly legible letters at least four inches high “WARNING - NO LIFE GUARD ON DUTY and RISK OF DROWNING - SUPERVISE CHILDREN CLOSELY”.
COS: facility hung up signs for last year with correct height requirements for letters
Re-inspection
Re-inspection
chlorine observed at 13.5ppm, maintain between 2-10ppm
pH observed at 7.0, maintain between 7.2-7.8
Routine
pH observed at 7.0, maintain between 7.2-7.8
skimmers not pulling
Permit/Opening
Permit/Opening
Regulation: .17((1)(c) - proper disinfectant level
Observed chlorine at 11ppm
C/A: maintain between 2-10ppm
flow meter range is not correct for pool; unable to accurately determine flow rate
Re-inspection
Routine
Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.
Observed pH at 7.0. C/A: pH shall be maintained between 7.2 and 7.8
Regulation: 511-3-5-.10(1)(c )1.ii. - (ii) the fitting shall not constitute a hazard to the user.
Observed floor return inlet in the 8ft end missing a cover.
C/A: The fitting shall not constitute a hazard to the user
Permit/Opening
Permit/Opening
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
Observed pH at 7.0. C/A: pH shall be maintained between 7.2 and 7.8
Permit/Opening
Add vomit/fecal and inclement weather procedures in pump room.