Jun 27, 2025
Routine
28 - flow meter: appropriate range and location
13-190(a)(7) Adequately sized flow meter shall be installed to accurately indicate flow. Observation: Flow meter not working.
1945 SAVOY DR ATLANTA, GA 30341
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Routine
13-190(a)(7) Adequately sized flow meter shall be installed to accurately indicate flow. Observation: Flow meter not working.
Permit/Opening
13-190(a)(7) Adequately sized flow meter shall be installed to accurately indicate flow. Observation: Flow meter not working.
13-187(c)Current inspection shall be posted. Observation: no inspection report posted
13-202(i) Observed no emergency action plan available at the time of inspection
Permit/Opening
13-188(h)(4) Leak at lower end of the pool continuously spilling water onto deck (worse when water features are off). Please repair and correct so water is not spilling from pool onto deck.
13-191(a) All valves and piping in equipment room shall be clearly labeled. Observation: some things labeled; some were not. Flow direction unclear.
13-201(c)(4) No hot water available in dressing showers.
Permit/Opening
13-188(h)(4) Leak at lower end of the pool continuously spilling water onto deck (worse when water features are off). Please repair and correct so water is not spilling from pool onto deck.
13-191(a) All valves and piping in equipment room shall be clearly labeled. Observation: some things labeled, some were not.
13-201(c)(4) No hot water available in dressing showers.
13-198(a) Feature pump not located within pump room. All pool equipment must be located within an enclosed room or completed enclosed area.
Permit/Opening
Permit/Opening
13-202(g) An operable, hardwired, weatherproof telephone, with direct 911 access or capability installed in a conspicuous location shall be readily available at all times. Observed 911 phone inoperable.
13-189(c)(1) - The free-chlorine residual in all parts of the pool shall be no less than 3ppm. Observed the free-chlorine residual at 2.34ppm.
13-201(b) A shower with tempered water with a temperature range maintained between 70F and 104F. Advised to turn on water heater for deck shower closest to the pool.
13-202(i) Each pool facility shall have in place a departmentally approved EAP. Observed chemical emergency evacuation plan, emergency crisis plan, water rescue and injury emergency plan, and drill procedures for emergency situations missing from EAP. CPO took picture of EAP template.
Permit/Opening
13-189(c)(1) - The free-chlorine residual in all parts of the pool shall be no less than 3ppm. Observed the free-chlorine residual at 0.29ppm.
13-197(i) - No disinfectant added by hand as the sole or primary method of adding disinfectant. Observed CPO hand-feeding Clorox into the pool. COS: CPO stopped pouring Clorox into the pool. Advised CPO that if he is caught again doing that, he and the property manager will be issued a tickets.
13-197(a) The water in each pool shall be continuously chemically treated with an approved disinfecting agent with associated approved equipment. Observed chlorinators filled with chlorine tablets, but unable to chlorinate the pool. Advised to fix chlorinators so that chlorine can be added into the pool by approved chlorinators.
13-190(a) All circulation equipment must be maintained. Observed missing inlet cap. Advised to replace missing inlet cap.
13-201(b) A shower with tempered water with a temperature range maintained between 70F and 104F. Advised to turn on water heater for deck shower closest to the pool.
13-202(i) Each pool facility shall have in place a departmentally approved EAP. Observed chemical emergency evacuation plan, emergency crisis plan, water rescue and injury emergency plan, and drill procedures for emergency situations missing from EAP. CPO took picture of EAP template.