Jun 5, 2026
Permit/Opening
1600 WINTERS CREEK DR ATLANTA, GA 30360
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Permit/Opening
Permit/Opening
Permit/Opening
13-190(a): Equipment shall obtain one turnover every six hours (86 GPM). Observed: 55 GPM.
13-190(a): All circulation equipment shall function properly and be maintained. One return inlet was not capped.
13-189(c)(2): Cyanuric acid levels shall not exceed 100ppm. Observed: 128ppm.
13-201(c)(3): Lavatories shall be provided with tempered water. There was no hot water in bathroom.
Permit/Opening
13-189(c)(1): Pool shall maintain pH level of 7.2-7.8 at all times. Observed: 7.1.
13-189(c)(2): Cyanuric acid levels shall not exceed 100ppm. Observed: 145ppm.
13-201(c)(3): Lavatories shall be provided with tempered water. There was no hot water in bathroom.
Permit/Opening
13-189(c)(1): Code says chlorine should be 3.0-10.0ppm -Observed chlorine at 0.30ppm
13-202(d): Code says there must be a 14 foot sheppard's pole and hook and a ring buoy with a rope attached to it -Observed no pole or rope
13-190(a)(7): Code says flow meter should be operable -Observed flow meter to be stuck
13-202(c): Code says the pool shall have a place to record pool parameters -Observed no place
13-184(e)(5): Code says unsecured handrails are an imminent health hazard -Observed pole to come out of ground
13-201(k): Code says bathrooms must have liquid soap, toilet paper, and paper towels -Observed none
13-202(i): Code says there must be an emergency action plan -Observed no plan -DeKalb County Board of Health number and CPO number must be placed by emergency phone