13-202(a)(2) Entry into the pool area shall be at the shallow end of the pool through a self-closing, self-latching gate or door that has a positive-latching mechanism mounted at least 45” above the ground surface directly below the gate.
13-189(c)(2)Cyanuric Acid levels shall not exceed 100ppm
13-184(e)(5)Unsecured handrails considered an imminent health /safety hazard
#37 Missing weirs in skimmers
Permit/Opening
Observed the flow rate at 90gpm. The equipment shall be operated continuously on a 24- hour basis to obtain the minimum required of 4 turnover per day, or one turnover every 6 hours. For a 37,000 gallon pool, the minimum flow rate is 103 gpm.
Permit/Opening
Observed magnetic strip not properly functioning to maintain gate and door closed. 13-202(a)(2) Entry into the pool area shall be at the shallow end of the pool through a self-closing, self-latching gate or door that has a positive-latching mechanism mounted at least 45” above the ground surface directly below the gate.
13-189(c)(1) A free chlorine residual in all parts of the pool shall be maintained between 3-10ppm. Observed chlorine test at .33ppm.
An adequately sized flow meter shall be installed on the return line to accurately indicate the circulation rate. Observed flow meter not functioning.
Permit/Opening
13-190(a)The equipment shall be operated continuously to obtain the minimum of one turnover every six hours. Flow reading was low at time of inspection.
Permit/Opening
13-189(c)(1) A free chlorine residual of no less than 3ppm shall be maintained at all times. This was observed to be less at time of inspection.
13-189(c)(1) Alkalinity was higher than the specified pH range in code which between 7.2-7.8
13-189(a) The water in pool shall be continually chemically treated with an approved disinfecting agent, with associated approved equipment, whereby the residual can easily be measured. The chlorine residual reading was low and chlorinator was not working at time of inspection.
13-193(a) Pressure gauges damaged at inspection, each sand filter must have adequate working pressure gauges.
13-202(d) Each pool shall be equipped with a shepherds hook attached to a non-telescoping pole. The hook was detachable at time of inspection.
13-205(a)(1) A minimum of one turnover every six hours is required for pools.
13-190(a) A minimum of one turn over is required every six hours for pools.
13-196(a)(4) Each skimmer shall have a properly designed and operating weir, three of four weirs were missing.