4580 BARCLAY DR ATLANTA, GA 30338
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Permit/Opening
Observed emergency phone was inoperable during inspection.
13-202(g) An operable, hard wired, weatherproof telephone with direct 911 access or capability installed in a conspicuous location shall be readily available at all times within the pool enclosure.
Permit/Opening
13-188(d)(1): Permanent Slip resistant, easily readable depth markers at least 4 inches high. Must be black letters and numbers on a background in feet and inches.
Observation: No depth markers on the pool surface/deck. Only markers present are inside the pool wall/waterline.
113-188(d)(2): At shallow portions of the pool "No Diving" must be minimum 2 inches tall.
Observation: No diving markers present.
Permit/Opening
Code: V;13-188(d)(2) Code says that "No Diving" markers must be kept at depths of minimum of five feet or less and must be consistent around all perimeters of the pool. Obs: "No diving" observed to be inadequate sizing and location. Must be at least 4 inches high.
Re-inspection
13-188(d)(2): At shallow portions of the pool, there shall be "No Diving" in minimum 2 inch letters. "No diving" can only be used in conjunction with words. obs: "No diving" observed to be smaller than 2 inches tall.
13-188(h)(4): Decks shall not retain any standing water greater/longer than 20 minutes. Obs: Multiple wet areas that are significant in size. Some areas have darkened due to prolonged wetness.
Routine
13-189(c)(1): Chlorine shall be measured at range of 3-10. Obs: chlorine was measured at 2.90.
13-189(c)(2): pH must be measured at range of 7.2-7.8. Obs: pH was measured at 8.0.
13-188(d)(2): At shallow portions of the pool, there shall be "No Diving" in minimum 2 inch letters. "No diving" can only be used in conjunction with words. obs: "No diving" observed to be smaller than 2 inches tall.
13-196(a)(4): each skimmer shall provide effective skimming. Obs: All skimmers were full of debris. CPO cleaned it.
13-188(h)(4): Decks shall not retain any standing water greater/longer than 20 minutes. Obs: Multiple wet areas that are significant in size. Some areas have darkened due to prolonged wetness.
Permit/Opening
13-188(d)(2): Code says "No Diving" must be in at least (2) two inch black lettering -Only observed universal "No Diving" logo which is not allowed by itslef