May 6, 2026
Routine
28 - flow meter: appropriate range and location
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter not measuring the appropriate GPM, meter should be reading a minimum of 100GPM, observed nozzle stuck at 60GPM. CA: Advised PIC a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided. The flow indicator shall be capable of measuring from one-half to at least one and one-half times the design flow rate. The gauge shall be located after the filtering equipment and in such location on the return line, so as to measure the total amount of water returning to the pool according to the manufacturer’s installation specifications.
12 - grab/hand rails, ladders installed and secure
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed 2 hand rails loose, PIC has been advised to repair and provide update once repairs are made. CA: Advised PIC Handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.