1570 SHERIDAN RD ATLANTA, GA 30324
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Permit/Opening
13-202(a)(2): Entry shall be through self-closing and self-latching gates. Observed 1 gate not self-latching.
13-202(g): An operational phone with 911 access shall be readily available at all times. Observed phone operational with heavy static and feedback, informed by 911 operator that they could not hear me clearly.
13-202(d): Pool shall have a coast guard approved lifesaving ring firmly attached to a 1/4"-3/8" diameter throwing rope as long as 1 1/2 times max pool width, or 50 feet, whichever is longer. Observed life ring without throwing rope.
13-190(a): equipment shall be operated to obtain a minimum turnover rate of 1 every 6 hours. The minimum flow meter reading for a 6 hour turnover rate for this pool is 117gpm. Observed flow meter at 60 gpm.
13-202(m): safety rules must have minimum 12 required statements. Observes rules sign missing several statements, provided CPO with required statements list.
13-201(k): an adequate supply of liquid body soap shall be provided in dressing showers at all times. Observed no body soap.
13-187(c): Inspection report shall be displayed at all times. Observed no inspection report posted.
13-189(c)(1): Pool shall have an approved test kit. Observed test kit chemicals expired.
13-187(c): Permit shall be displayed at all times. Observed permit not displayed.
Permit/Opening
Routine
13-190(a):The equipment shall be operated on a twenty-four(24) hour basis to obtain the minimum required number of six(6) hours (pools).
13-190(a)(7):An adequately sized flow meter shall be installed on the return lint to accurately indicate the circulation rate in gallons per minute(GPM); Observed the flow meter rate at 60, but should be at 116.
Routine
13-189(c)(1): The free-chlorine residual in all parts of the pool shall be maintained at a concentration of no less than three parts per million (3ppm) at all times. Observed no chlorine in the pool at 0.00.
13-197(i): No disinfectant added by hand as the sole or primary method of adding disinfectant or pH control chemicals. Observed the chemical feeder was not feeding the disinfectant.
13-196(a)(4): Each skimmer shall have a properly designed and operating weir for skimming. Observed a dead mouse in skimmer.
13-201(k): At all times, an adequate supply of liquid soap, toilet paper and paper towels shall be provided and stored in appropriate dispensers conveniently accessible to users. Observed no soap or paper towels and bathrooms need to be cleaned.
13-187(c):The current inspection report shall be displayed in a conspicuous place where it is easily readable by the public at all times. Observed last years inspection was only posted.
Permit/Opening
13-190 (a) Observed flow meter not reaching appropriate turnover rate, reading 60 minimum needed is 116
Permit/Opening
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter not reaching appropriate turnover rate, reading 60 minimum needed is 116