Jun 18, 2025
Permit/Opening
19 - adequate turnover rate
13-190(a)The equipment shall be operated continuously on a twenty-four (24) hour basis on order to meet minimum turnover rate. Observed flow meter at 50gpm should be 94gpm
5816 COVINGTON HWY DECATUR, GA 30035
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
13-190(a)The equipment shall be operated continuously on a twenty-four (24) hour basis on order to meet minimum turnover rate. Observed flow meter at 50gpm should be 94gpm
Permit/Opening
13-189(c)(6) At all times, the water shall be of such clarity that the main drains are clearly, visible from the deck. Observed water was cloudy
13-202(g) An operable, hard-wired, weatherproof telephone with direct 911 access. Observed 911 phone did not work.
13-189(c)(1) Free-chlorine must be no less than 3ppm not to exceed 10 ppm. Observed chlorine was below standard.
13-189(c)(1) The pool shall be maintained in an alkaline condition with a pH level between 7.2 - 7.8. Observed pH is higher than standard.
13-202(c) Each pool operator shall maintain a daily record of operating information. The records to be made available for inspection shall include data on disinfectant level, pH, maintenance. Observed CPO did not produce a pool log.
13-196(a)(4) Each skimmer shall have a properly designed and operating weir. Observed weir is missing.
13-187(c) A copy of the pool operator's certificate shall be conspicuously displayed near the operating permit. Observed no CPO cert displayed.
13-202(i)-need Emergency Action plan. Observed no EAP was produced.
Routine
13-190(a)(7) An adequately sized flow meter shall be installed on the return line to accurately indicate the circulation rate in gallons per minute. Flow meter not working at time of inspection.
13-202(k) Pool shall be supplied with readily available first aid kit equipped to treat at least 15 people. First aid kit empty at inspection.
Routine
13-190(a) The equipment shall be operated continuously to obtain the minimum requirement of one full turnover every six hours.
13-190(a)(7) An adequately sized flow meter shall be installed on the return line to accurately indicate the circulation rate in gallons per minute. Flow meter not working at time of inspection.