Redan, DeKalb County

COVINGTON GLEN APARTMENTS

5816 COVINGTON HWY DECATUR, GA 30035

Pool
Latest score
95
Jun 18, 2025
City
Redan
County
DeKalb
Inspections
4

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Jun 18, 2025

Permit/Opening

Score: 951 violation

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-190(a)The equipment shall be operated continuously on a twenty-four (24) hour basis on order to meet minimum turnover rate. Observed flow meter at 50gpm should be 94gpm

Jun 2, 2025

Permit/Opening

Score: 718 violations

4 - water clarity: main drains clearly visible

15 ptsCorrected: NoRepeat: No

13-189(c)(6) At all times, the water shall be of such clarity that the main drains are clearly, visible from the deck. Observed water was cloudy

5 - emergency phone operational and accessible

15 ptsCorrected: NoRepeat: No

13-202(g) An operable, hard-wired, weatherproof telephone with direct 911 access. Observed 911 phone did not work.

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: No

13-189(c)(1) Free-chlorine must be no less than 3ppm not to exceed 10 ppm. Observed chlorine was below standard.

7 - ph between 7.2 and 7.8

15 ptsCorrected: NoRepeat: No

13-189(c)(1) The pool shall be maintained in an alkaline condition with a pH level between 7.2 - 7.8. Observed pH is higher than standard.

36 - daily recordkeeping: water testing and self inspection performed

5 ptsCorrected: NoRepeat: No

13-202(c) Each pool operator shall maintain a daily record of operating information. The records to be made available for inspection shall include data on disinfectant level, pH, maintenance. Observed CPO did not produce a pool log.

17 - skimmers/gutters maintained and operable

4 ptsCorrected: NoRepeat: No

13-196(a)(4) Each skimmer shall have a properly designed and operating weir. Observed weir is missing.

32 - operator training certification available onsite and approved

4 ptsCorrected: NoRepeat: No

13-187(c) A copy of the pool operator's certificate shall be conspicuously displayed near the operating permit. Observed no CPO cert displayed.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-202(i)-need Emergency Action plan. Observed no EAP was produced.

Jul 31, 2023

Routine

Score: 942 violations

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

13-190(a)(7) An adequately sized flow meter shall be installed on the return line to accurately indicate the circulation rate in gallons per minute. Flow meter not working at time of inspection.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-202(k) Pool shall be supplied with readily available first aid kit equipped to treat at least 15 people. First aid kit empty at inspection.

Jun 6, 2023

Routine

Score: 902 violations

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-190(a) The equipment shall be operated continuously to obtain the minimum requirement of one full turnover every six hours.

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

13-190(a)(7) An adequately sized flow meter shall be installed on the return line to accurately indicate the circulation rate in gallons per minute. Flow meter not working at time of inspection.