Routine
Regulation: .17((1)(c) - proper disinfectant level
Observed high chlorine. Must be maintained at 2-10ppm. Fix within 3 days.
Observed CYA above maximum at 100ppm. Cya Stabilizer (if used) Cyanuric acid,ppm Ideal: 30-50 Maximum: 90
Permit/Opening
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter missing. A flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided
Regulation: 511-3-5-.18(3)(h) - (h) depth markers number and letters shall be tile and four inches minimum in height. numbers shall be of contrasting color to the background on which they are applied.
Observed depth markers missing around wade pool. Depth markers number and letters shall be tile and four inches minimum in height. Numbers shall be of contrasting color to the background on which they are applied.
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
Observed CYA above maximum at 100ppm. Cya Stabilizer (if used) Cyanuric acid,ppm Ideal: 30-50 Maximum: 90
Re-inspection
Observed air bubbles coming in through inlets. Must be repaired. Slight sand coming in through inlets.
Re-inspection
Observed ph below 7.0. Must be between 7.2-7.8
Routine
Observed Chlorine at 0ppm. Must be between 2-10
Permit/Opening
Regulation: 511-3-5-.18(3)(h) - (h) depth markers number and letters shall be tile and four inches minimum in height. numbers shall be of contrasting color to the background on which they are applied.
Observed depth markers missing, needed on deck around wade pool.
Regulation: 511-3-5-.10(1)(c )1.ii. - (ii) the fitting shall not constitute a hazard to the user.
Observed air bubbles coming in through inlets. Must be repaired.
No flow meter present. Must be installed.