May 23, 2025
Re-inspection
28 - flow meter: appropriate range and location
Observed flow meter float stuck at bottom of meter. Must be repaired or replaced.
7485 HUNTERS RIDGE DR DOUGLASVILLE, GA 30134
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Re-inspection
Observed flow meter float stuck at bottom of meter. Must be repaired or replaced.
Re-inspection
Regulation: 511-3-5-.23(5)(a) - (a) during operation, disinfectant levels are less than the minimum level specified in dph rule 511-3-5-.17. if the level of the disinfectant used is not specified in dph rule 511-3-5-.17, the disinfectant must be approved and kept at levels determin
Observed chlorine at 0.5 ppm. Maintain between 2-10ppm
Permit/Opening
Observed access gate unable to self-latch. CA: Access gates must be self-latching.
Regulation: .17((1)(c) - proper disinfectant level
Observed chlorine at 0.5 ppm. Maintain between 2-10ppm
Routine
Observed access gate unable to self-latch. CA: Access gates must be self-latching.
Unable to access and assess pump room and equipment. CA: Access needed
Permit/Opening
Re-inspection
Observed gauge on second filter not working. Must be repaired/replaced before routine inspection.
Permit/Opening
Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates
Observed access gate unable to self-close or self latch. CA: Access gates must be self-closing and self-latching.
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Observed emergency phone with dial tone however, unable to dial 911. CA: Emergency phone must be able to dial 911 and work properly.
Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.
Observed pH too high above 8. CA: pH must be between 7.2-7.8
Regulation: 511-3-5-.23(5)(c ) - (c) the pump, automatic disinfectant equipment, or other equipment necessary for continuous filtration and disinfection of the swimming pool, spa, or recreational water park attraction is not working or is unable to maintain adequate turnover rate.
Observed both filters at 0psi. CA: Filter must be operating properly.
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter low at 20 gpm. CA: Flow meter must be at appropriate range.