May 20, 2025
Permit/Opening
2110 LEGACY PARK DR LITHIA SPRINGS, GA 30122
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
Emergency phone inoperable CA: Must operate to connect to 9-1-1
Observed Chlorine too high at 22 ppm. Chlorine must be between 2-10ppm.
Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.
Observed last log on log sheet of 06/20/23. CA: A safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed hand rail on step not secure. CA: Must be installed secured.
Observed suspected leak in pump room due to pooling of water around pump equipment. Observed chemicals on floor of pump room. CA: Repair leak. Keep chemicals at least 6 inches from floor
Permit/Opening
Regulation: 511-3-5-.19(2)(k) - (k) fixtures shall be designed so that they may be readily and frequently cleaned and
Water leaks in Restrooms. Men's room Sink and woman's room toilet. CA: Repair water leaks
Deck has a hole in the paver section with lounge chair side towards the entrance road. CA: Repair.
Permit/Opening
Permit/Opening
Regulation: .17((1)(c) - proper disinfectant level
Observed Chlorine too high at 12 ppm. Chlorine must be between 2-10ppm.
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter not operating showing 0ppm. Flow meter must operate properly.