St. Simons, Glynn County

King and Prince Hotel (South Villa Pool)

201 NEPTUNE RD UNIT 10000 SAINT SIMONS ISLAND, GA 31522

Pool
Latest score
98
Mar 25, 2026
City
St. Simons
County
Glynn
Inspections
6

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Mar 25, 2026

Permit/Opening

Score: 981 violation

16 - pool deck: maintained, unobstructed and clean

Regulation: 511-3-5-.06(1)(l) - (l) open joints or gaps larger than three-sixteenths inch wide or with vertical elevations exceeding 1/4 inches shall be rectified using appropriate fillers. construction joints where pool coping meets the decks shall be watertight and shall not allo

2 ptsCorrected: NoRepeat: No

Observed plaster damage in shallow end. CA: Replaster/ patch needed for spot in shallow end before the 2027 season or may not be re permitted.

Sep 11, 2025

Routine

Score: 912 violations

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: No

Observed combined chlorine above 0.4ppm at the time of this inspection. CA: Lower combined chlorine to 0.4ppm or less.

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

Observed CYA above 90ppm at the time of this inspection. CA: Lower CYA to 90ppm or less.

Apr 2, 2025

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Nov 19, 2024

Routine

Score: 951 violation

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

flow meter not working at the time of this inspection. ca: replace to ensure reading properly

Mar 25, 2024

Permit/Opening

Score: 981 violation

16 - pool deck: maintained, unobstructed and clean

Regulation: 511-3-5-.06(1)(l) - (l) open joints or gaps larger than three-sixteenths inch wide or with vertical elevations exceeding 1/4 inches shall be rectified using appropriate fillers. construction joints where pool coping meets the decks shall be watertight and shall not allo

2 ptsCorrected: NoRepeat: No

Observed wear on pool surface, near stairs, at the time of this inspection. CA: Keep eye, patch/resurface if continues to get worse.

Aug 22, 2023

Routine

Score: 942 violations

21 - cyanuric acid level not exceeding maximum

Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br

4 ptsCorrected: NoRepeat: No

Observed CYA above 90ppm at the time of this inspection. CA: Lower CYA to 90ppm or less.

16 - pool deck: maintained, unobstructed and clean

Regulation: 511-3-5-.06(1)(l) - (l) open joints or gaps larger than three-sixteenths inch wide or with vertical elevations exceeding 1/4 inches shall be rectified using appropriate fillers. construction joints where pool coping meets the decks shall be watertight and shall not allo

2 ptsCorrected: NoRepeat: No

Observed slight wear on pool surface at the time of this inspection. CA: Keep eye, patch/resurface if continues to get worse.