May 7, 2026
Routine
***Note: An informal inspection will occur by 5/15/2026. Total Rooms: 129 Rooms Inspected: 130, 211, 218, 309, 312, 320, 321,409, 410, 413, 418, 511, 513. Questions? (770)-963-5132 www.gnrhealth.com ***Note: Facility has requested an extension for the bathroom mechanical vents. Extension was given and an informal inspection will occur by 06/08/2026.***
-
17: .08(5)Observed the mechanical ventilation fans in the guestroom bathrooms not operating in rooms 320, 413, and 409. [.08(5)] Toilet, lavatory and bathing facilities shall be mechanically ventilated. Where ventilation ducts are used, ducts from toilet rooms shall not be connected into return ventilation ducts to any other room. In existing tourist accommodations permitted prior to the adoption of this rule, the current ventilation must prevent odor, mold, mildew, and moisture. All new or major renovation of a tourist accommodation will require mechanical ventilation to be installed to the outside of the building separate from heating and air-condition systems.