KATHLEEN, Houston County

Joy Park

1151 HWY 96 KATHLEEN, GA 31047

Pool
Latest score
100
Apr 28, 2026
City
KATHLEEN
County
Houston
Inspections
4

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Apr 28, 2026

Routine

Score: 1000 violations
No violations recorded for this inspection.

Sep 23, 2025

Routine

Score: 991 violation

30 - deck/rinse shower maintained

1 ptsCorrected: NoRepeat: No

Water supply to shower/drinking fountain combo is off. Keep unit supplied with water.

Aug 8, 2025

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Aug 6, 2025

Permit/Opening

Score: 794 violations

6 - proper disinfectant level

Regulation: .17(1)(a)(b) - proper disinfectant level

15 ptsCorrected: NoRepeat: No

Observed pool only having 0.5ppm of free chlorine. Free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound keep free chlorine in the allowable range of 1-10ppm. Add chlorine to the pool.

7 - ph between 7.2 and 7.8

Regulation: 511-3-5-.17(2) - (2) chemical values: ph

15 ptsCorrected: NoRepeat: No

Observed the pH at a 7 ppm. The allowable range of pH is 7.2-7.8 ppm. Add chemicals to raise the pH.

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

The flow meter has been changed out from a flow meter that would read up to 1000 to one that only reads to 400 and the flow cylinder on the inside is maxed at the top unable to get a correct flow reading. Change the flow meter back to the original one.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

Observed alkalinity at 30ppm. The allowable range is 60-180 ppm with an ideal range of 80-120 ppm. Add chemicals to raise alkalinity.