May 19, 2026
Permit/Opening
1010 S HOUSTON LAKE RD WARNER ROBINS, GA 31088
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Re-inspection
Routine
Observed that neither of the gates are automatically closing. The auto closing mechanisms are missing. Gates into the pool area must automatically close and latch. Repair the gates to they will automatically close and latch. Keep pool closed until repaired and a satisfactory inspection is made. Call 478-951-4465 to schedule a reinspection.
Re-inspection
Routine
Regulation: 511-3-5-.23(5)(a) - (a) during operation, disinfectant levels are less than the minimum level specified in dph rule 511-3-5-.17. if the level of the disinfectant used is not specified in dph rule 511-3-5-.17, the disinfectant must be approved and kept at levels determin
Observed the pool having 1.5ppm of chlorine. The allowable range for pool with stabilizer is 2-10ppm. Add chlorine so that it is in the allowable range.
Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.
Observed the pH below 7.0ppm. The allowable range of pH is 7.2-7.8ppm. Add chemicals to raise the pH.
Permit/Opening
Routine
Permit/Opening
Permit/Opening
Regulation: .17(1)(a)(b) - proper disinfectant level
Observed the pool only having .5ppm of chlorine. The allowable chlorine range for pool without stabilizer is 1ppm-10ppm. Raise chlorine concentration.
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
Observed pH values at an 8.0. The allowable range of pH is 7.2-7.8. Lower pH to the allowable range.
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed the flow meter not working and stuck at the bottom of the measuring tube. Fix flow meter so that it is measuring the rate of flow through the filter system.
Routine
Flow meter stuck. Keep flow meter functional so flow rate can be determined.