Mar 9, 2026
Followup
6-1A - proper cold holding temperatures
Regulation: 511-6-1.04(6)(f) - time/temperature control for safety; cold holding (p)
Observed food stored in prep cooler not maintain at 41F or below as of required. The range temperature for the chicken where between 55F and 56F. CA; All time temperature control for safety control shall be held at 41F or below for cold holding violation. COS: All concerned food were discarded
4-2B - food-contact surfaces: cleaned & sanitized
Regulation: 511-6-1.05(6)(n) - manual and mechanical warewashing equipment, chemical sanitization-temperature, ph, concentration, hardness (p,pf)
A mix of detergent and chlorine was stated by employees as the method use to sanitized the dinning table. Also, employee use the same mix detergent and chlorine for wiping cloth use to clean the prep surface in main kitchen. CA: Ensure to use sanitizer to clean and sanitized the dining table and prep table. If chlorine sanitizer is used, ensure the concentration is 100ppm
16B - plumbing installed; proper backflow devices
Regulation: 511-6-1.06(2)(r) - system maintained in good repair (p, c)
Handwashing sink not in good repair
13A - posted: permit/inspection/choking poster/handwashing
Regulation: 511-6-1.02(1)(d) - displaying of the inspection report (c)
Current inspection was not displayed
15A - food and nonfood-contact surfaces cleanable, properly designed, constructed, and used
Regulation: 511-6-1.05(6)(q)1&3 - good repair & calibration (c)
Walk-in cooler not in good repair gasket must be replaced.
15A - food and nonfood-contact surfaces cleanable, properly designed, constructed, and used
Regulation: 511-6-1.05(6)(q)1&3 - good repair & calibration (c)
Prep cooler must be service due to ambient temperature from 40F to 46F and cannot maintain food 41F or below
15B - warewashing facilities: installed, maintained, used; test strips
Regulation: 511-6-1.05(3)(b),(c) - manual warewashing, sink compartment requirement; drainboards (pf, c)
4 compartment sink not properly labeled
17C - physical facilities installed, maintained, and clean
Regulation: 511-6-1.07(1)(a) - indoor materials (c)
Bare concrete floor in back dry storage, prep area, and part of the kitchen