Apr 27, 2026
Permit/Opening
Score: 1000 violations
No violations recorded for this inspection.
926 STEVENS CREEK RD AUGUSTA, GA 30907
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
Regulation: 511-3-5-.17(4) - (4) stabilizer (if used) cyanuric acid,ppm ideal: 30-50 maximum: 90 comments: if stabilizer is: too high: - may reduce chlorine efficacy too low: - chlorine residual rapidly destroyed by sunlight note: stabilizer is not needed in indoor or br
Observed CYA around 100. C/A: Reduce CYA to 90 or below.
Permit/Opening
Routine
OBSERVED TURNOVER RATE OF 7.03. C/A: HAVE TURNOVER RATE ADJUSTED TO 6.0 OR BELOW.
Permit/Opening