Macon, Bibb County

Red Carpet Inn

2870 JEFFERSONVILLE RD MACON, GA 31217

Tourist
Latest score
85
Sep 8, 2025
City
Macon
County
Bibb
Inspections
4

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Sep 8, 2025

Routine

Score: 855 violations

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: Yes

EHS observed no gas-inspection records on the premises. When asked, PIC was unable to proved records. PIC stated that he was new to the facility and unsure of when the last inspection was performed and who to contact for an inspection.

511-6-2-.15(5) - Heating and Fire Safety-Inspection All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency

CA: Informed PIC of the annual gas-fired inspection requirement, local storage of inspection records, and advised to have an inspection performed as soon as possible, if no prior inspection can be found. Discussed that DPH inspection forms are available if needed

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: Yes

EHS Observed:

Room 116: Opaque, white mold-like substance on the exterior of the dresser holding the tv Room 223: Dead insects found on carpet, on AC unit, and within dresser and bedside drawers Room 207: Apparent dirt-like substance within bedside and dresser drawers Room 108: Apparent dirt-like substance within bedside drawer

511-6-2-.14(5) - Condition of Furnishings All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin.

CA: Advised PIC to increase cleaning frequency of room furnishings and carpets

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

EHS Observed:

  • Stains on the mattress pads of rooms: 108, 207, 115, and 223
  • Hairs on the sheets of rooms: 108, 115, and 207
  • Apparent burn holes in the mattress pad of room: 115
  • Stains on exterior of pillows of rooms: 223 and 207

511-6-2-.14(6) - Bed, Bedding, and Linens Washable mattress pads or covers shall be used on all mattresses. Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin. Each bed shall be provided, as a minimum, with two sheets and one pillow and pillowcase. After each occupancy and upon the request of the occupant, sheets and pillowcases shall be changed with fresh laundered linens. During occupancy, linens shall be changed at a minimum frequency of not less than weekly.

CA: Advised PIC to clean and replace linen with stains and/or hairs. Advised PIC to dispose of and replace linen with burn holes

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

EHS Observed: "Clean" linen stored in laundry room with hair on them

511-6-2-.14(6) - Bed, Bedding, and Linens Washable mattress pads or covers shall be used on all mattresses. Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin. Each bed shall be provided, as a minimum, with two sheets and one pillow and pillowcase. After each occupancy and upon the request of the occupant, sheets and pillowcases shall be changed with fresh laundered linens. During occupancy, linens shall be changed at a minimum frequency of not less than weekly.

CA: Requested PIC to pool linen with hair and rewash. Advised PIC that if hairs are unable to be removed that linen should be replaced

16 - toilet/lavatory/bathing facility fixtures and rooms clean and maintained; properly lighted, clearly marked, proper signage, and all in good repair

Regulation: 511-6-2-.08(4) - toilet facilities-cleaning and maintenance

2 ptsCorrected: NoRepeat: No

EHS Observed:

Room 223: Cobwebs throughout the ceiling of the bathroom

511-6-2-.08(4) - Toilet Facilities-Cleaning and Maintenance Toilet rooms and fixtures must be smooth and nonabsorbent and shall be kept clean and in good repair. Walls, floors, and ceilings shall be kept clean and in good repair.

CA: Advised PIC to clean ceiling of bathroom

Dec 13, 2024

Routine

Score: 863 violations

3 - hot/cold running water under pressure in all required locations of tourist accommodation

Regulation: 511-6-2-.07(2) - hot water supply

5 ptsCorrected: NoRepeat: Yes

Observed several rooms water temperature were either too low or too high: 114 (124F), 210 (130F), 211 (130F), 201 (86F).

511-6-2-.07(2) - Hot Water Supply Cold running water under pressure shall be provided to all equipment that uses water. Hot and cold running water under pressure shall be provided to all lavatories, bathing facilities, laundry facilities, and water-using equipment where eating and drinking utensils are washed. In all new tourist accommodations, and where possible in existing tourist accommodations, hot water in all guest rooms shall not exceed 120F.

Corrective Action: Spoke with PIC, they alternate water heaters. Spoke about finding right spot for water temperature

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: Yes

Observed no gas-fire equipment record on premises; PIC could not provide.

511-6-2-.15(5) - Heating and Fire Safety-Inspection All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency

Corrective action: Spoke with PIC, mentioned inspection occurred, but they don't leave her any documentation. Will send gas-fire equipment inspection sheet to have signed with each inspection. Explained it needs to be annually

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: Yes

Observed:

114: air conditioner filter dirty 210: air conditioner filter dirty, lightbulbs need replacing, smoke detector detached from wall 211: air conditioner filter dirty, smoke detector detached from wall, lightbulbs need replacing 201: air conditioner filter dirty

511-6-2-.14(5) - Condition of Furnishings All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin.

Corrective action: Spoke with PIC, to have air conditioner filters cleaned, lightbulbs replaced and smoke detector re attached to walls

Jan 31, 2024

Routine

Score: 826 violations

3 - hot/cold running water under pressure in all required locations of tourist accommodation

Regulation: 511-6-2-.07(2) - hot water supply

5 ptsCorrected: NoRepeat: Yes

EHS observed overhot water in rooms 114 (129), 211 (145), 210 (140). Temperature in F in parens.

In all new tourist accommodations, and where possible in existing tourist accommodations, hot water in all guest rooms shall not exceed 120F.

EHS instructed PIC to turn down water temperature in affected rooms

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: No

PIC was unable to provide up to date gas-fired inspection report for EHS to inspect. PIC stated that inspection would be scheduled within 5 days to bring facility into compliance. Last gas-fired report marked 10/3/2022.

511-6-2-.15(5) - Heating and Fire Safety-Inspection All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency.

EHS advised PIC to attain gas-fired inspection to maintain at facility

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: No

PIC was unable to provide up to date gas-fired inspection report for EHS to inspect. PIC stated that inspection would be scheduled within 5 days to bring facility into compliance. Last gas-fired report marked 10/3/2022.

511-6-2-.15(5) - Heating and Fire Safety-Inspection All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency.

EHS advised PIC to attain gas-fired inspection to maintain at facility

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: No

EHS observed damaged and dusty filters for AC units in rooms 114.

511-6-2-.14(5) - All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin.

EHS advised PIC to replace or clean AC filters more frequently

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: No

EHS observed damaged upholstery including stains and physical damage on chairs in rooms 114, 211, 210.

11-6-2-.14(5) - Condition of Furnishings All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: Yes

EHS observed damage to comforters including holes and cigarette burns in all rooms inspected. EHS observed stains on pillowcases in rooms 114, 121, 211, 210. EHS observed stained sheets in rooms 114, 121, 211. EHS observed damaged sheets in rooms 114, 121, 211, 210.

511-6-2-.14(6) - Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin.

EHS instructed PIC to discard too-badly damaged linens and to increase frequency of or quality of housekeeping efforts re: linens

Aug 29, 2023

Routine

Score: 893 violations

3 - hot/cold running water under pressure in all required locations of tourist accommodation

Regulation: 511-6-2-.07(2) - hot water supply

5 ptsCorrected: NoRepeat: No

EHS observed in rooms 108, 114, 114 hot water exceeding 120 degrees.

Cold running water under pressure shall be provided to all equipment that uses water. Hot and cold running water under pressure shall be provided to all lavatories, bathing facilities, laundry facilities, and water-using equipment where eating and drinking utensils are washed. In all new tourist accommodations, and where possible in existing tourist accommodations, hot water in all guest rooms shall not exceed 120F.

EHS informed PIC that temperatures shall not exceed 120F, and to adjust water heater down to meet standard

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

EHS observed stained bedding in rooms 114, 108 on pillowcases and sheets.

Washable mattress pads or covers shall be used on all mattresses. Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin. Each bed shall be provided, as a minimum, with two sheets and one pillow and pillowcase. After each occupancy and upon the request of the occupant, sheets and pillowcases shall be changed with fresh laundered linens. During occupancy, linens shall be changed at a minimum frequency of not less than weekly.

Informed PIC to increase cleaning frequency of bedding and pillowcases

10 - permit and inspection report current and properly displayed; pic assigned

Regulation: 511-6-2-.04(1)a - permit display

2 ptsCorrected: NoRepeat: No

EHS observed out of date inspection score posted in office by primary window, dated 10/18/22.

Violation Code Reference 511-6-2-.04(1)a - Permit Display Any person operating a tourist accommodation shall obtain and display a valid DPH tourist accommodation permit issued by the Health Authority. (b) To qualify for a permit, an applicant shall:

  1. Be an owner of the tourist accommodation;
  2. Allow access to the tourist accommodation;
  3. Provide all information as required on the application and pay all applicable local and state fees referenced in DPH Rule 511-6-2-.22 at the time the application is submitted and;
  4. Score 100% on the permitting inspection for newly constructed facilities.

EHS informed PIC of the need to post current physical printout of inspection report