Macon, Bibb County

Manchester at Wesleyan (Pool 1)

1665 WESLEYAN DR MACON, GA 31210

Pool
Latest score
100
Apr 30, 2026
City
Macon
County
Bibb
Inspections
5

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Apr 30, 2026

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Apr 23, 2026

Permit/Opening

Score: 793 violations

2 - self-closing / self-latching gates

Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates

15 ptsCorrected: NoRepeat: Yes

Observed multiple entrance gates that could not self-close and self-latch. (h) Access gates shall also comply with the requirements of this Rule and shall be equipped to accommodate a locking device. Barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. Pedestrian access gates shall be self-closing and have a self-latching device. Gates other than pedestrian access gates shall have a self-latching device. Where the release mechanism of the self latching device is located less than fifty-four inches from the bottom of the gate, 1. The release mechanism shall be located on the pool side of the gate at least three inches below the top of the gate and 2. Any openings in the gate or barrier located within eighteen inches of the release mechanism shall be less than one-half inch. 3. Mechanisms controlled by an access card reader, key entry device or keypad shall be located on the outside of the access gate. EHS informed the PIC(maintenance) of the need to have all gates to self-close and self-latch.

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: No

Observed high combined chlorine level. (1) Disinfectant Levels (a) Free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.EHS informed the PIC of the need to balance the water chemistry as the initial free chlorine reading was extremely high.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

Observed inner wall pool light not mounted. Facility is aware of the need to mount securely.

Mar 31, 2026

Permit/Opening

Score: 805 violations

2 - self-closing / self-latching gates

Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates

15 ptsCorrected: NoRepeat: No

Observed multiple entrance gates that could not self-close and self-latch. (h) Access gates shall also comply with the requirements of this Rule and shall be equipped to accommodate a locking device. Barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. Pedestrian access gates shall be self-closing and have a self-latching device. Gates other than pedestrian access gates shall have a self-latching device. Where the release mechanism of the self latching device is located less than fifty-four inches from the bottom of the gate, 1. The release mechanism shall be located on the pool side of the gate at least three inches below the top of the gate and 2. Any openings in the gate or barrier located within eighteen inches of the release mechanism shall be less than one-half inch. 3. Mechanisms controlled by an access card reader, key entry device or keypad shall be located on the outside of the access gate. EHS informed the PIC(maintenance) of the need to have all gates to self-close and self-latch.

5 - emergency phone operational and accessible

Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim

15 ptsCorrected: NoRepeat: No

Observed the emergency phone not operating. (c) An operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all times. The emergency phone shall be capable of connecting to 911 and electronically transferring an automatic number identification and automatic locator identification of the pool emergency phone to the public safety answering point, if available. A 911 sign or the names and phone numbers of the nearest available police, fire, ambulance service or rescue unit shall be posted nearby. EHS informed the PIC of the need to fix the phone and for it to dial to Macon-Bibb 911.

6 - proper disinfectant level

Regulation: .17((1)(c) - proper disinfectant level

15 ptsCorrected: NoRepeat: No

Observed no chlorine present in the pool. (c) Free Chlorine level in pools using cyanuric acid or a stabilized chlorine product; Minimum 2.0 Ideal 2.0-5.0 Maximum 10.0EHS informed the CPO of the need to balance the water chemistry.

8 - chemical feeder operational and approved

Regulation: 511-3-5-.16(1) - (1) disinfectant equipment and chemical feeders, such as flow-through chemical feeders, electrolytic chemical generators, mechanical chemical feeders, chemical feed pumps, and automated controllers shall comply with the requirements of nsf standard 5

15 ptsCorrected: NoRepeat: No

Observed feeder leaking water. (1) Disinfectant equipment and chemical feeders, such as flow-through chemical feeders, electrolytic chemical generators, mechanical chemical feeders, chemical feed pumps, and automated controllers shall comply with the requirements of NSF Standard 50.

EHS informed CPO to determine the source of the leak.

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

Observed flow meter not operating. capable of measuring from (b) A flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided. The flow indicator shall be capable of measuring from one-half to at least one and one-half times the design flow rate. The gauge shall be located after the filtering equipment and in such location on the return line, so as to measure the total amount of water returning to the pool according to the manufacturer’s installation specifications. EHS informed the PIC(maintenance) of the need to fix or replace the flow meter.

Jul 3, 2025

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Jun 18, 2025

Permit/Opening

Score: 793 violations

2 - self-closing / self-latching gates

Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates

15 ptsCorrected: NoRepeat: No

Observed multiple entrance gates that could not self-close and self-latch. (h) Access gates shall also comply with the requirements of this Rule and shall be equipped to accommodate a locking device. Barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. Pedestrian access gates shall be self-closing and have a self-latching device. Gates other than pedestrian access gates shall have a self-latching device. Where the release mechanism of the self latching device is located less than fifty-four inches from the bottom of the gate, 1. The release mechanism shall be located on the pool side of the gate at least three inches below the top of the gate and 2. Any openings in the gate or barrier located within eighteen inches of the release mechanism shall be less than one-half inch. 3. Mechanisms controlled by an access card reader, key entry device or keypad shall be located on the outside of the access gate. EHS informed the PIC(maintenance) of the need to have all gates to self-close and self-latch.

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

Observed flow meter not operating. capable of measuring from (b) A flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (GPM) and accurate within ten percent actual flow shall be provided. The flow indicator shall be capable of measuring from one-half to at least one and one-half times the design flow rate. The gauge shall be located after the filtering equipment and in such location on the return line, so as to measure the total amount of water returning to the pool according to the manufacturer’s installation specifications. EHS informed the PIC(maintenance) of the need to fix or replace the flow meter.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

Observed high pressure gauge reading; pool potentially needing to be backwashed. EHS informed the PIC of the issue and he stated that it needed to be backwashed.