Macon, Bibb County

SLEEP INN

3928 RIVER PLACE DR MACON, GA 31210

Tourist
Latest score
95
Jan 27, 2026
City
Macon
County
Bibb
Inspections
5

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Jan 27, 2026

Routine

Score: 951 violation

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: No

EHS observed no gas-fired equipment inspection on record for view at the time of inspection. The PIC indicated that their sprinkler system was inspected recently, and she believes the gas-fired equipment inspection was also performed at that time.

511-6-2-.15(5) - Heating and Fire Safety-Inspection All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency

CA: EHS advised the PIC that all gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. If records are found, EHS recommended that they be stored locally so that records are available to staff and for view by the EHS during future inspections

Aug 5, 2025

Routine

Score: 912 violations

3 - hot/cold running water under pressure in all required locations of tourist accommodation

Regulation: 511-6-2-.07(2) - hot water supply

5 ptsCorrected: NoRepeat: Yes

EHS observed the exceeding water temperatures in rooms: 119, 115, 103, and 101.

CA-PIC needs to contact maintenance to adjust the water heater so the hot water in the rooms will not be exceeding 120 degrees.

511-6-2-.07(2) - Hot Water Supply Cold running water under pressure shall be provided to all equipment that uses water. Hot and cold running water under pressure shall be provided to all lavatories, bathing facilities, laundry facilities, and water-using equipment where eating and drinking utensils are washed. In all new tourist accommodations, and where possible in existing tourist accommodations, hot water in all guest rooms shall not exceed 120F

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: No

EHS observed dusty air filters in rooms 115 and 101.

CA-PIC needs to make sure that housekeeping is routinely cleaning air filter to reduce dust build up.

511-6-2-.14(5) - Condition of Furnishings All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin

Jan 14, 2025

Routine

Score: 863 violations

3 - hot/cold running water under pressure in all required locations of tourist accommodation

Regulation: 511-6-2-.07(2) - hot water supply

5 ptsCorrected: NoRepeat: No

EHS observed the exceeding water temperatures in rooms: 121, 115, 111, and 107.

A-PIC needs to contact maintenance to adjust the water heater so the hot water in the rooms will not be exceeding 120 degrees.

511-6-2-.07(2) - Hot Water Supply Cold running water under pressure shall be provided to all equipment that uses water. Hot and cold running water under pressure shall be provided to all lavatories, bathing facilities, laundry facilities, and water-using equipment where eating and drinking utensils are washed. In all new tourist accommodations, and where possible in existing tourist accommodations, hot water in all guest rooms shall not exceed 120F

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: Yes

EHS requested for the gas-fire inspection report. PIC did not have access to the files during the time of the inspection.

Corrective action- PIC needs to have a copy of the gas-fire inspection report accessible at the property. This inspection is completed annually by a certified inspector.

511-6-2-.15(5) - Heating and Fire Safety-Inspection All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: Yes

EHS observed dusty air filters from all the rooms that were observed.

CA-PIC needs to make sure that housekeeping is routinely cleaning all each air filter in all rooms.

511-6-2-.14(6) - Bed, Bedding, and Linens Washable mattress pads or covers shall be used on all mattresses. Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin. Each bed shall be provided, as a minimum, with two sheets and one pillow and pillowcase. After each occupancy and upon the request of the occupant, sheets and pillowcases shall be changed with fresh laundered linens. During occupancy, linens shall be changed at a minimum frequency of not less than weekly

Apr 12, 2024

Routine

Score: 912 violations

8 - annual gas fired equipment inspection on file; gas units equipped with automatic safety and/or 100% cut-off pilot

Regulation: 511-6-2-.15(5) - heating and fire safety-inspection

5 ptsCorrected: NoRepeat: No

EHS requested for the gas-fire inspection report. PIC did not have access to the files during the time of the inspection.

511-6-2-.15(5) - Heating and Fire Safety-Inspection All gas-fired equipment shall be inspected at least annually by a qualified licensed contractor or local fire authority, if available. Points to be inspected are proper construction and installation, malfunctions and adjustments of controls and burners, faulty heat exchangers and vent obstructions. Any defects found on inspection must be corrected by a qualified heating contractor prior to use of the equipment. Upon request, the operator shall provide evidence of inspection and/or correction of any deficiency

Corrective action- PIC needs to have a copy of the gas-fire inspection report accessible at the property. This inspection is completed annually by a certified inspector

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

4 ptsCorrected: NoRepeat: No

EHS observed the following rooms:

Room 110- air filter needs to be cleaned. Room 113- Air filters need to be cleaned. Room 105-Hair on mattress pad and red stain on mattress pad. Room 102-Yellow stain on mattress stain on mattress pad and ac unit needs t be cleaned.

511-6-2-.14(6) - Bed, Bedding, and Linens Washable mattress pads or covers shall be used on all mattresses. Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin. Each bed shall be provided, as a minimum, with two sheets and one pillow and pillowcase. After each occupancy and upon the request of the occupant, sheets and pillowcases shall be changed with fresh laundered linens. During occupancy, linens shall be changed at a minimum frequency of not less than weekly

Aug 9, 2023

Routine

Score: 884 violations

27 - all furniture, waste receptacles, draperies, carpets; clean, and in good repair, considered the property of and furnished by the tourist accommodation

Regulation: 511-6-2-.14(5) - condition of furnishings

4 ptsCorrected: NoRepeat: No

EHS observed curtains that needed to be cleaned. It was rooms 103, room 105, and 106. Also, in room 106 the refrigerator had stains inside of it.

511-6-2-.14(5) - Condition of Furnishings All furniture, draperies, appliances, carpets, and other accessories, in the tourist accommodation, whether the property of the tourist accommodation owner or not, shall be considered the property of and furnished by the tourist accommodation for purposes of enforcement of this Chapter, and must be maintained in good repair, clean, and free of vermin

Correct of action- Make sure that housekeeping is properly cleaning the curtains in each room or replace. Correct by 8/09/2023

28 - beds, mattresses, mattress pads, springs, frames, pillows, and bed coverings clean; vermin free and in good condition; bed linen properly supplied, changed and laundered

Regulation: 511-6-2-.14(6) - bed, bedding, and linens

4 ptsCorrected: NoRepeat: No

EHS observed hair on mattress pad in room 102 and 103.

511-6-2-.14(6) - Bed, Bedding, and Linens

Correct of action- Making sure that housekeeping is cleaning the mattress pads or they can replace them with brand new mattress pads. Washable mattress pads or covers shall be used on all mattresses. Beds, mattresses, springs, slats, mattress pads, mattress and bed coverings, pillow and pillow covers shall be clean and free from vermin. Each bed shall be provided, as a minimum, with two sheets and one pillow and pillowcase. After each occupancy and upon the request of the occupant, sheets and pillowcases shall be changed with fresh laundered linens. During occupancy, linens shall be changed at a minimum frequency of not less than weekly.

Corrective action- Making sure that housekeeping clean each mattress pad after each use. Correct by 8/09/2023

17 - proper ventilation; no sign of mold, mildew, odors or moisture

Regulation: 511-6-2-.08(5) - toilet and bathing ventilation

2 ptsCorrected: NoRepeat: No

EHS observed mold like substances on the bathroom ceiling. The mold like substances were observed in rooms 103,105, and 106.

511-6-2-.08(5) - Toilet and Bathing Ventilation Toilet, lavatory and bathing facilities shall be mechanically ventilated. Where ventilation ducts are used, ducts from toilet rooms shall not be connected into return ventilation ducts to any other room. In existing tourist accommodations permitted prior to the adoption of this rule, the current ventilation must prevent odor, mold, mildew, and moisture. All new or major renovation of a tourist accommodation will require mechanical ventilation to be installed to the outside of the building separate from heating and air-condition systems.

Correct of action- Make sure they have proper ventilation. Also to make sure they are properly cleaning the bathrooms

25 - floors, walls, ceilings, windows, doors clean, and in good repair; appropriate for location and operation

Regulation: 511-6-2-.14(1) - floors, walls, and ceilings

2 ptsCorrected: NoRepeat: No

EHS observed a hole in the wall by the AC unit.

511-6-2-.14(1) - Floors, Walls, and Ceilings Floors, walls, ceilings. windows, doors and all other appurtenances shall be of sound construction, properly maintained in good repair and shall be kept clean. In all new constructed and extensively remodeled residential kitchens used in bed and breakfast inns, coved base molding may be required. Walls and ceilings in residential kitchens shall be easily cleanable and light colored.

Corrective action- To inform maintenance of the hole in the wall so they can properly fix it. Correct by 8/9/2023