Richmond Hill, Bryan County

Sterling Creek At Richmond Hill

45 LULLWATER DR RICHMOND HILL, GA 31324

Pool
Latest score
98
Mar 18, 2026
City
Richmond Hill
County
Bryan
Inspections
7

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Mar 18, 2026

Permit/Opening

Score: 981 violation

12 - grab/hand rails, ladders installed and secure

Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.

2 ptsCorrected: NoRepeat: No

Observed hand rails near fountain area able to be pulled from ground. C.A. Make sure hand rails are installed in away they cannot be removed.

Oct 22, 2025

Routine

Score: 725 violations

2 - self-closing / self-latching gates

Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates

15 ptsCorrected: NoRepeat: No

Observed gate open at time of inspection. CA gate shall self close and latch. Repair gate so that it self closes and latches.

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: No

Observed a combine chlorine level above .4 PPM. CA Lower combined chlorine level to below .4 PPM.

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.

5 ptsCorrected: NoRepeat: No

Observed that facility was not testing daily.CA A safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.

16 - pool deck: maintained, unobstructed and clean

Regulation: 511-3-5-.06(1)(l) - (l) open joints or gaps larger than three-sixteenths inch wide or with vertical elevations exceeding 1/4 inches shall be rectified using appropriate fillers. construction joints where pool coping meets the decks shall be watertight and shall not allo

2 ptsCorrected: NoRepeat: No

Observed holes and cracks on pool deck area. CA repair damaged pool deck areas with approved materials.

29 - toilets & lavatories: clean, maintained, and stocked

Regulation: 511-3-5-.19(2)(i) - (i) soap, paper towels, and toilet tissue shall be provided in all dispensers.

1 ptsCorrected: NoRepeat: No

Observed that bathrooms were missing hand drying provisions in both restrooms. Observed that women's restroom did not have hand washing soap available at time of inspection.

Aug 14, 2025

Re-inspection

Score: 942 violations

17 - skimmers/gutters maintained and operable

Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.

4 ptsCorrected: NoRepeat: No

Observed weirs missing at time of inspection. CA replace weirs.

16 - pool deck: maintained, unobstructed and clean

Regulation: 511-3-5-.06(1)(l) - (l) open joints or gaps larger than three-sixteenths inch wide or with vertical elevations exceeding 1/4 inches shall be rectified using appropriate fillers. construction joints where pool coping meets the decks shall be watertight and shall not allo

2 ptsCorrected: NoRepeat: No

Observed damaged to deck area. CA repair damaged deck areas.

Aug 5, 2025

Routine

Score: 746 violations

2 - self-closing / self-latching gates

Regulation: 511-3-5-.18(11)(h) - (h) access gates shall also comply with the requirements of this rule and shall be equipped to accommodate a locking device. barrier gates shall open away from the pool in facilities constructed after adoption of this chapter. pedestrian access gates

15 ptsCorrected: YesRepeat: No

Observed gate open at time of inspection. CA gate shall self close and latch. COS Gate was locked.

6 - proper disinfectant level

Regulation: .17((1)(c) - proper disinfectant level

15 ptsCorrected: NoRepeat: No

Observed a free chlorine level of .72 at time of inspection. CA raise chlorine levels to a range of 2.0-10.0 PPM.

11 - appropriate lifesaving equipment present

Regulation: 511-3-5-.18(10)(a) - (a) a light, strong pole not less than twelve feet long including body hook.

15 ptsCorrected: YesRepeat: No

Observed that facility did not have body hook assembled at time of inspection. COS hook was assembled and placed for public use.

28 - flow meter: appropriate range and location

Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from

5 ptsCorrected: NoRepeat: No

Observed that flow meter was not functioning at time of inspection.

36 - daily recordkeeping: water testing and self inspection performed

Regulation: 511-3-5-.22(12) - (12) a safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.

5 ptsCorrected: NoRepeat: No

Observed that facility was not testing daily. A safety self-inspection shall be conducted daily by the trained operator or responsible person and documented on a log sheet.

29 - toilets & lavatories: clean, maintained, and stocked

Regulation: 511-3-5-.19(2)(i) - (i) soap, paper towels, and toilet tissue shall be provided in all dispensers.

1 ptsCorrected: NoRepeat: No

Observed that bathrooms were missing hand drying provisions in both restrooms. Observed that women's restroom did not have hand washing soap available at time of inspection.

Feb 26, 2025

Permit/Opening

Score: 951 violation

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: No

Observed a combine chlorine level above .4. CA Lower combined chlorine level to below .4 PPM.

Mar 26, 2024

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

May 16, 2023

Re-inspection

Score: 951 violation

18 - combined chlorine level 0.4 ppm or less

Regulation: 511-3-5-.17(1) - (1) disinfectant levels (a) free chlorine, ppm in pools not using cyanuric acid or a stabilized chlorine compound use (b),1.-5.

5 ptsCorrected: NoRepeat: No

Observed combine chlorine level above 0.4. C.A. Make sure combine chlorine level is under 0.4.