May 18, 2026
Permit/Opening
1200 BRIDGEMILL AVE CANTON, GA 30114
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Re-inspection
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed hand rail of pool stairs near life guard station loose / not secure. Must fix.
Routine
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Observed 911 phone not working at time of inspection. This was corrected on sight and replaced with a voiceover IP phone, however, the address on file for the 911 operator is 1190 Bridgemill Ave and not 1200 Bridgemill Ave. 1190 Bridgemill Ave is the address for the clubhouse, which is too far from the pool to be acceptable as the 911 address. Must update 911 address to "1200 Bridgemill Ave Pool Phone".
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meters in pump room A broken and unable to read turnover rate. Must fix flow meters.
Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
Observed weirs missing in some skimmers. All skimmers must have a weir installed.
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed hand rail of pool stairs near life guard station loose / not secure. Must fix.
Permit/Opening
Re-inspection
Routine
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
Observed a pH of 8.0. The pH must be between 7.2-7.8
Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Observed a turnover rate of 550 GPM. The required turnover rate for this pool is 645 GPM.
Permit/Opening
Routine