Aug 18, 2025
Re-inspection
3470 MT. ZION RD STOCKBRIDGE, GA 30281
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Re-inspection
Permit/Opening
Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Observed pool not meeting adequate turnover rate. Advised to adjust
Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
Observed missing weirs. Advised to obtain
Regulation: 511-3-5-.06(3)(f)1. - 1. handrails, if removable, shall be installed in such a way that they cannot be removed without the use of tools.
Observed loose grab railings. Advised to tighten. COS: grab railings were tightened
Regulation: 511-3-5-.18(12)(c) - (c) the same sign in subsection (b) above or an additional sign will state under the heading “pool risks” the following items in clearly legible letters at least one inch high:
Observed no standard pool risk sign for Ga and the incorrect warning no lifeguard on duty sign
Permit/Opening
Regulation: 511-3-5-.18(13)(c) - (c) a sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.
No maximum occupancy sign posted- Must say Maximum Occupancy and not bather load.