Jun 13, 2025
Re-inspection
1800 BARRETT LAKES BLVD NW KENNESAW, GA 30144-4567
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Re-inspection
Permit/Opening
Regulation: 511-3-5-.07(1)(e ) - (e) water clarity shall be maintained. when standing at the pool's edge at the deep end, the main drain suction outlet covers or a four inch by four inch square marker tile in contrasting color shall be clearly visible. when standing at a spa's e
Unable to see main drain. Ensure main drain is visible.
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
pH observed above 8. maintain between 7.2 and 7.8
Regulation: 511-3-5-.18(10)(b) - (b) a minimum one-fourth inch diameter throwing rope one and one-half times the maximum width of the pool or fifty feet in length, whichever is less, to which has been firmly attached a ring buoy with an outside diameter of approximately fifteen inch
Ensure life ring has roped attached
Observed flow meter not working. C/a repair or replace flow meter
Re-inspection
Routine
Regulation: 511-3-5-.23(5)(a) - (a) during operation, disinfectant levels are less than the minimum level specified in dph rule 511-3-5-.17. if the level of the disinfectant used is not specified in dph rule 511-3-5-.17, the disinfectant must be approved and kept at levels determin
chlorine observed at 1ppm, maintain between 2-10ppm
Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.
pH observed below 7, maintain between 7.2-7.8
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
clean or replace flow meter
Regulation: 511-3-5-.11(3)(g) - (g) the skimmer equalizer lines shall be protected by an approved cover/grated with a flow rating equal the maximum system flow divided by the number of skimmers in the system or the maximum flow rating of the skimmer, whichever is greater.
skimmers not pulling
Re-inspection
Permit/Opening
Regulation: .17((1)(c) - proper disinfectant level
Chlorine too high at 17. CA: Chlorine concentration required to be 2-10 ppm.
Flow meter stuck in place. CA: Repair/replace.
Regulation: 511-3-5-.22(2) - (2) the trained operator shall have a current certificate showing completion of an approved operator training course. a copy or the original certificate or documentation shall be available onsite for inspection by the health authority.
No proof of valid CPO certificate on site. CA: Post certificate.
No peak occupancy sign posted. Cas: Post.
Re-inspection
Permit/Opening
No chlorine detected. CA: 2-10 ppm Cl required.
pH observed at 8.0. CA: 7.2-7.8 pH required.
Float line not in place.