Jun 11, 2025
Routine
17 - skimmers/gutters maintained and operable
Skimmers full of debris and not pulling
2121 WINDY HILL RD MARIETTA, GA 30060-6402
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Routine
Skimmers full of debris and not pulling
Routine
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flowmeter stuck or broken. C/A- ensure flow meter is working or replaced
Regulation: 511-3-5-.18(13)(c) - (c) a sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.
Observed no pool hours or peak occupancy established. C/A- A sign shall be posted stating the hours of operation in clear view near the entrance and shall state the theoretical peak occupancy.
Re-inspection
Regulation: 511-3-5-.23(5)(a) - (a) during operation, disinfectant levels are less than the minimum level specified in dph rule 511-3-5-.17. if the level of the disinfectant used is not specified in dph rule 511-3-5-.17, the disinfectant must be approved and kept at levels determin
Observed chlorine at 11.5ppm - correct immediately.
Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
All skimmers missing weirs.
Routine
Regulation: 511-3-5-.07(1)(e ) - (e) water clarity shall be maintained. when standing at the pool's edge at the deep end, the main drain suction outlet covers or a four inch by four inch square marker tile in contrasting color shall be clearly visible. when standing at a spa's e
Water cloudy, unable to see main drains.
Regulation: 511-3-5-.23(5)(a) - (a) during operation, disinfectant levels are less than the minimum level specified in dph rule 511-3-5-.17. if the level of the disinfectant used is not specified in dph rule 511-3-5-.17, the disinfectant must be approved and kept at levels determin
Chlorine observed at 13ppm.
Regulation: 511-3-5-.11(3)(d) - (d) each skimmer shall have a weir that adjusts automatically to variations in water level over a minimum range of four inches.
Skimmers missing weirs, need to be cleaned.
Routine
Provide a light inside the shower in the restrooms
Routine
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flowmeter stuck or broken. C/A- ensure flow meter is working or replaced
Routine