Jun 9, 2026
Routine
1625 ROSWELL RD MARIETTA, GA 30062
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Routine
Permit/Opening
Routine
Observed unsecure ladder. CA: Fix/Tighten
Permit/Opening
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter at 80gpm; should be ~150gpm
C/A: replace flow meter; it is undersized
Regulation: 511-3-5-.10(1)(c )1.ii. - (ii) the fitting shall not constitute a hazard to the user.
Observed return inlet cover missing on one of the floor inlets
C/A: The fitting shall not constitute a hazard to the user.
Re-inspection
Routine
Regulation: 511-3-5-.23(5)(a) - (a) during operation, disinfectant levels are less than the minimum level specified in dph rule 511-3-5-.17. if the level of the disinfectant used is not specified in dph rule 511-3-5-.17, the disinfectant must be approved and kept at levels determin
Observed chlorine at 11ppm
Regulation: 511-3-5-.23(5)(b) - (b) during operation, the ph is less than the minimum or more than the maximum levels allowed in dph rule 511-3-5-.l7.
Observed pH at 7.0
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Flow meter unable to accurately display flow rate; indicator not moving
Permit/Opening
Routine