May 30, 2025
Permit/Opening
580 FRANKLIN GTWY SE MARIETTA, GA 30067
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Permit/Opening
Regulation: .17((1)(c) - proper disinfectant level
Observed chlorine at 16.5ppm
C/A: chlorine shall be maintained between 2-10ppm
Routine
Regulation: 511-3-5-.10(1)(c )1.ii. - (ii) the fitting shall not constitute a hazard to the user.
Observed return inlet over missing; the one closest to the 3ft grab/handrail.
Permit/Opening
Permit/Opening
Regulation: 511-3-5-.17(2) - (2) chemical values: ph
Observed pH at 7.0ppm. C/A: pH shall be maintained between 7.2 and 7.8ppm
Regulation: 511-3-5-.07(4)(b) - (b) a flow meter measuring the rate of flow through the filter system with an appropriate range readable in gallons per minute (gpm) and accurate within ten percent actual flow shall be provided. the flow indicator shall be capable of measuring from
Observed flow meter with a range not high enough to accurately display the flow rate. C/A: The flow indicator shall be capable of measuring from one-half to at least one and one-half times the design flow rate.
Routine
Permit/Opening