Atlanta, DeKalb County

GABLES EMORY POINT

855 EMORY POINT DR ATLANTA, GA 30329

Pool
Latest score
76
Jun 12, 2026
City
Atlanta
County
DeKalb
Inspections
6

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Jun 12, 2026

Permit/Opening

Score: 765 violations

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: No

13-189(c)(1): Free-chlorine residual shall be between 3.0 - 10.0 ppm. Observed chlorine at a 2.04 ppm.

8 - chemical feeder operational and approved

15 ptsCorrected: NoRepeat: No

13-197(a): Pool disinfectant must be administered continuously and through approved equipment. Observed that the salt cell was not working and the erosion chlorine feeder did not contain any chlorine tablets. Unable to verify that the chlorinator was working.

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-205(b)(1): Pools with features must have a complete turnover every 4 hours. Observed the flowrate at 100 GPM, must be at least 167 GPM.

21 - cyanuric acid level not exceeding maximum

4 ptsCorrected: NoRepeat: No

13-189(c)(2): Cyanuric acid levels shall not exceed 100 ppm. Observed levels at 120 ppm.

21 - cyanuric acid level not exceeding maximum

4 ptsCorrected: NoRepeat: No

13-189(c)(2): Cyanuric acid levels shall not exceed 100 ppm. Observed levels at 120 ppm.

Jul 2, 2025

Routine

Score: 982 violations

29 - toilets & lavatories: clean, maintained, and stocked

1 ptsCorrected: NoRepeat: No

13-201(c)(3) - pool bathrooms must have sinks with running tempered water observed: one sink not operational. Recommended to repair as soon as possible. - no imminent health hazard

30 - deck/rinse shower maintained

1 ptsCorrected: NoRepeat: No

13-201(b) - Deck shower must be operational with tempered water observed: deck shower was not operational

Jun 5, 2025

Permit/Opening

Score: 951 violation

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-205(b)(1) - pools with features must have complete turnover every 4 hours observation: The flowmeter showed a flow rate that created a complete turnover greater than 4 hours. the turnover rate does not meet the required turnover every 4 hours.

Jun 3, 2025

Permit/Opening

Score: 796 violations

7 - ph between 7.2 and 7.8

15 ptsCorrected: NoRepeat: No

13-189(c)(1) - pH of pool water must be between 7.2-7.8 observed: pH of pool water was 7.9

7 - ph between 7.2 and 7.8

15 ptsCorrected: NoRepeat: No

13-189(c)(1) - pH of pool water must be between 7.2-7.9 observation: pH of pool water was 7.9

  • imminent health hazard -

8 - chemical feeder operational and approved

15 ptsCorrected: NoRepeat: No

13-197(a)- pool disinfectant must be administered continuously & through approved equipment observation: erosion chlorine feeder did not contain any chlorine tablets, & thus was not operational -imminent health hazard-

11 - appropriate lifesaving equipment present

15 ptsCorrected: NoRepeat: No

13-202(d) - pool should have attached and operational Shepherd's hook attached to a non-telescoping pole length of 14 feet & a Coast Guard approved lifesaving ring buoy attached to a throwing rope. Pools over 50 feet in length are required to have additional sets of lifesaving equipment observation: of two sets of appropriate life-saving equipment, one Shephard's hook was unattached, and one ring buoy did not have an attached rope -imminent health hazard-

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-205(b)(1) - pools with features must have complete turnover every 4 hours observation: the turnover rate does not meet the required turnover every 4 hours

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-207(i)- Each pool facility shall have an approved Emergency Action Plan, with all required sections observation: The pool facility did not contain a Emergency Action Plan with all required sections

Jul 18, 2024

Routine

Score: 851 violation

5 - emergency phone operational and accessible

15 ptsCorrected: NoRepeat: No

13-202(g) An operable, hard-wired, weatherproof telephone, with direct 911 access... shall be readily available at all times within the pool enclosure. Emergency phone is inoperable.

Jul 3, 2023

Permit/Opening

Score: 904 violations

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

13-190(a): for this 40,000 gallon pool the flow meter shall read at 111gpm to achieve the required 6 hr turnover; I observed 45gpm

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

13-190(a)(7): an adequately sized flow meter shall be installed on the return line to accurately indicate the circulation rate; I observed a flow meter with a max of 120gpm when it should be at least 165gpm

17 - skimmers/gutters maintained and operable

4 ptsCorrected: NoRepeat: No

13-196(a)(4): each skimmer shall have a property designed and operating weir; I observed no weirs in the skimmers, made an advisement to get weir before next inspection

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-188(h)(9): a minimum of 1 covered and lined trash receptacle shall be provided; I observed 3 trashcans in the pool area all with no lid