May 29, 2026
Permit/Opening
19 - adequate turnover rate
13-205(b)(1) The equipment shall be operated continuously on a 24 hour basis to obtain the minimum required number of 1 turnover every 6 hours for standard pools. Turnover rate was low. Flow meters read ~100 gpm instead of the required 277.77 gpm.