Apr 28, 2026
Permit/Opening
1218 WARRENHALL LN ATLANTA, GA 30319
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
13-190(a): Equipment shall be operated continuously on a 24 hour basis.
Observation: Based on 180,000 gallons, their flow meter should be reading a minimum 750 gpm. Their flow meter is observed at 450 gpm.
180,000/240= 750gpm.
Permit/Opening
13-190(a): Equipment shall be operated continuously on a 24 hour basis to maintain required number of 1 turnover every 6 hours.
Turnover rate reads as 120, but minimum should be 500. Turnover rate from both flowmeters should be combined
13-188(a) Pool surfaces shall have no cracks or open joints. Observed cracks around the perimeter of pool.
Routine
13-190(a): Equipment shall be operated continuously on a 24 hour basis to maintain required number of 1 turnover every 6 hours. For a pool of 180,000 g, turnover rate should be greater than 500 gpm. Observed turnover rate of 400 gpm.
Permit/Opening
13-190(a): Maintain required number of 1 turnover every 6 hours. For a pool of 180,000 g, turnover rate should be greater than 500 gpm. Observed turnover rate of 140 gpm.
13-201(j) Bathroom trash cans must have covers. "Pool can open with this violation"
13-198(a-b) Equipment room light and ventilation fan not working. Both must work. Need to fix as soon as possible.
Routine
13-190(a): Maintain required number of 1 turnover every 6 hours. For a pool of 180,000 g, turnover rate should be greater than 500 gpm. Observed turnover rate of 425 gpm.
13-202(e): Lifeguard certifications available onsite. Observed lifeguard certifications were not present onsite, though could verify active certification online
13-188(d)(1): Depth markers indicated in both feet and inches. Observed pool depth markers on deck surface missing units.
13-191(a): All valves and piping in equipment room shall be clearly labeled. Observed arrows but missing specific labeling.
13-184(e)(5): Imminent health hazard if bathrooms are not in sanitary condition. Observed clogged toilet in men's bathroom. Corrected on site.
13-201(c)(3): Lavatory with tempered range of 70 - 104 degrees F. Observed sinks without hot water. Corrected on site.
13-197(k): Safe, secure storage of chemicals. Observed chemicals on the floor of the pump room. Advised to move to pallet/shelf.