Jun 4, 2026
Re-inspection
3524 BOWLING GREEN WAY DORAVILLE, GA 30340
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Re-inspection
Routine
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Emergency phone was not operational.
Permit/Opening
13-201(c)(4): 1 shower with tempered water between 70F and 104F shall be provided for each 100 women and 100 men. Observed no shower in womens restroom and no hot water or soap in mens. Pool can be open.
Routine
13-188(h)(3) A deck no less than 5' in width, shall surround a minimum of 65% of pool perimeter. The required deck shall be unobstructed in all directions and shall be constructed at the same elevation. Observed: Deck is obstructed by pool toys and trash can cause falling hazard
Routine
13-187 (c) a copy of the pool operator’s certificate shall be conspicuously displayed near the operating permit.
Other violations of the chapter: ring buoy near the kiddie pool is not coast guard approved, need to get rid of it and purchase a new one.
Permit/Opening
Re-inspection
Routine
13-189(c)(1): Chlorine should be maintained between 3 ppm and 10 ppm. Observed: Chlorine tests read 11.47 and 11.73 ppm.
13-189(c)(2): Cyanuric acid levels shall not exceed 100ppm. Observed: Cyanuric acid test read 118 ppm.
Routine
Permit/Opening
Routine
13-189(c)(1)- Pool must maintain 7.2-7.8 pH levels. Corrected to 7.4.
Re-inspection
Routine
13-202(h) Emergency phone shall be equipped with 911.
13-189(c)2 Cynauric acid levels shall not exceed 100ppm