Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
13-189(a)(5) All pools shall be kept free from sediment, dirt, or debris. Observed dirt and leaves in the shallow end of the pool.
Routine
13-202(k)Each pool shall be supplied with a readily available first aid kit. Container shall be durable and weather resistant
Permit/Opening
Routine
Regulation: 511-3-5-.18(10)(c ) - (c) an operable, hard-wired, conventional telephone line or continuous powered source, weatherproof emergency phone shall be permanently installed in a conspicuous location within the pool enclosure and must be readily available to bathers at all tim
Observed emergency phone power to be out of service and shut off. Emergency phone power was turned back on and corrected on site (COS).
Routine
Permit/Opening
Re-inspection
Routine
13-189(c)(1): Code says disinfectant must be 3.0-10.0ppm -First Reading: 14.04 -Second Reading: 14.75
13-190(a)(7): Code says flow meter must be adequately sized -Observed middle flow meter to be small and bobber to be upside down
Routine
13-189(c)(1): Code says pH must be between 7.2 and 7.8 -First Observation: 8.0 -Second Observation: 7.4 -COS
13-190(a): Code says there should be 1 turnover every 4 hours for pools with features Required turnover: 187.5 gpm Turnover observed: 75 gpm
Routine
13-189(c)(1): Code says pH must be between 7.2 and 7.8 -First Observation: 7.9 -Second Observation: 7.8 COS
13-190(a): Code says there should be 1 turnover every 4 hours for pools with features Required turnover: 187.5 gpm Turnover observed: 67 gpm
13-190(a)(7): Code says an adequately sized flow meter must be installed on the return drain -Flow meter on drain needs to be at least able to read 180 -Flow meter is too small, bigger one required