Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Routine
13-20(c)(3) Laboratory with tempered water with a temperature range of 70F to 104F shall be provided for each 100 men or women. There wasn't hot water coming out of the faucet in the male or female bathroom.
13-184(e)(5) Imminent health hazard exist if the sanitary facilities are not functional or if the facilities are not maintained in a clean and sanitary condition. One toilet in the female bathroom wasn't working.
13-189(a)(5) All pools shall be kept free from sediment, dirt, or debris. Observed sediment on the bottom of the pool.
Permit/Opening
Regulation: 511-3-5-.07(1)(a) - (a) the equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity. the turnover rate for pools constructed after the adoption of this chapter shall not exceed the sum of one and one-half times the average wat
Observed low turnover rate (330GPM). The turnover rate should be at least 389gpm in a 140,000 gallon pool.
CA:The equipment for a swimming pool shall be of adequate size to turn over the entire pool water capacity.
Observed brown dirt/debris at the bottom of the pool.
13-189(a)(5) All pools shall be kept free from sediment, dirt or debris by frequent brushing and vacuuming of the bottom and sidewalls. Visible scum shall be removed immediately.
CPO will have it cleaned in the next 72 hours. CPO will also reach out to HOA to have the pool resurfaced in the winter.
CPO will sent a photo of treated and cleaned stains by May 10th, 2025.
Routine
Regulation: 511-3-5-.23(3)(d) - (d) the operator shall receive a copy of the inspection and place it in a location protected from the weather and in public view as designated by the health authority.
Inspection report was not observed to be in public view.
Permit/Opening
13-190(a) Observed a flow rate of 280, based off pool volume flow rate should be 388GPM.
13-202(m) observed pool rules sign not meeting the minimum code requirements. Can be found on page 42 of the DeKalb County Pool Ordinance.
Routine
13-205(b)(1): Code says there must be 1 turnover every 6 hours -Flow needed: 388gpm -Flow observed: 260gpm
13-196(a)(4): Code says each skimmer must have an operable weir -Observed multiple weirs missing
13-199(d): Code says pools with diving boards must have a sign saying "one user at a time" -Observed no sign
13-187(c): Code says inspection must be in public view -Observed inspection not in public view
Routine
13-190(a): Code says there should be one turnover every 6 hours -Required flow rate: 388gpm -Observed flow rate: 340gpm
13-199(d): Code says that pools with a diving board should have a sign saying "only one user on the diving board at a time" -Observed no sign
13-187(c): Code says the previous inspection must be in public view -Observed no inspection
Routine
No Comment Recorded
13-190(a): Code says there should be one turnover every 6 hours -Required flow rate: 389gpm -Observed flow rate: 320gpm
13-199(d): Code says that pools with a diving board should have a sign saying "only one user on the diving board at a time" -Observed no sign
13-191(a): Code says piping must be identified and labeled -Observed equipment to not be identified
13-201(j): Code says a covered trash can must be present in bathrooms -Observed trashcan to not be covered in the women's room