Jun 10, 2026
Permit/Opening
19 - adequate turnover rate
13-190(a): Equipment shall be operated to obtain the minimum required turnover rate. The required turnover rate for this pool is 6 hours. The minimum flow meter reading to reach turnover for this pool is 139gpm. Observed flow meter reading of 90gpm.
17 - skimmers/gutters maintained and operable
13-196(a)(4): Each skimmer shall have a weir. Observed 3/4 skimmers missing a weir. No IHH at this time.
37 - other violations of the chapter
13-198(b): Ventilation of fresh air is required in all equipment rooms. Observed no ventilation in equipment room.
37 - other violations of the chapter
13-202(h): Telephone numbers for health department, CPO, and management office must be conspicuously posted. Observed inaccurate numbers posted.
37 - other violations of the chapter
13-202(h): Pool address must be posted at the emergency phone. Observed no address posted.