Jul 3, 2025
Permit/Opening
3421 N DRUID HILLS RD DECATUR, GA 30033
Inspection scores over time for this facility.
Georgia inspection history is score-based, with violations grouped under each recorded inspection.
Permit/Opening
Permit/Opening
13-189(c)(1) The free-chlorine residual in all parts of the pool shall be maintained at a concentration between 3-10ppm. Observed chlorine levels at 0.10ppm.
3-201(b)If no bathhouse is required, a shower with tempered water with a temperature range maintained between 70°F and 104°F shall be provided at each approved entrance into the pool area. Observed all showers around pool area not operable
Permit/Opening
Permit/Opening
3-190(a)(7)An adequately sized flow meter shall be installed on the return line to accurately indicate the circulation rate in gallons per minute
-observed flow meter sized too small for required turnover rate.
13-196(a)The actual water level shall be maintained within the operation water level range of the system’s skimmer weir device or gutter rim. Observed water levels below minimum; advised to maintain levels.