North Druid Hills, DeKalb County

ONE K APARTMENTS

1000 GABLES WAY NE ATLANTA, GA 30329

Pool
Latest score
100
Jun 12, 2026
City
North Druid Hills
County
DeKalb
Inspections
14

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Jun 12, 2026

Permit/Opening

Score: 1000 violations
No violations recorded for this inspection.

Jun 2, 2026

Permit/Opening

Score: 851 violation

5 - emergency phone operational and accessible

15 ptsCorrected: NoRepeat: No

13-202(g): An operable, hard wired, weatherproof telephone with direct 911 access shall be readily available at all times within pool enclosure. Observed emergency phone not operational

May 26, 2026

Permit/Opening

Score: 912 violations

36 - daily recordkeeping: water testing and self inspection performed

5 ptsCorrected: NoRepeat: Yes

13-189(c)(4): Pool water Chl and pH levels should be tested and recorded 2x daily. Observed log with 1 or fewer logs daily

21 - cyanuric acid level not exceeding maximum

4 ptsCorrected: NoRepeat: Yes

13-189(c)(2): Cyanuric acid levels should not exceed 100 ppm. Observed levels at 105 and 107. CPO instructed to drain and refill before re-inspection

May 22, 2026

Permit/Opening

Score: 912 violations

36 - daily recordkeeping: water testing and self inspection performed

5 ptsCorrected: NoRepeat: No

13-189(c)(4): Pool water Chl and pH levels should be tested and recorded 2x daily. Observed log with 1 or fewer logs daily. CPO was informed to increase number of logs in new book formatted for twice daily records.

21 - cyanuric acid level not exceeding maximum

4 ptsCorrected: NoRepeat: Yes

13-189(c)(2): Cyanuric acid levels should not exceed 100 ppm. Observed levels at 127 and then 125 after an hour of drain/refill. CPO instructed to drain and refill before re-inspection and to refrain from additional shocking/over-chlorination with the stabilized chlorine until proper levels are restored

Aug 21, 2025

Re-inspection

Score: 784 violations

6 - proper disinfectant level

15 ptsCorrected: YesRepeat: No

13-189(c)(1): a free-chlorine residual shall be maintained between 3ppm and 10ppm; this was corrected onsite: originally observed a chlorine level reading of 1.58ppm, but CPO brought level up to 3.42ppm.

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-205(b)(1): for an outdoor pool, a turnover rate of one turnover every six (6) hours shall be maintained; note the flow meter reading of 80gpm

30 - deck/rinse shower maintained

1 ptsCorrected: NoRepeat: No

13-201(b): if no bathhouse is required, a shower with tempered water shall be provided on the pool deck; observed that no such shower exists at time of inspection

34 - inspection report placed in public view

1 ptsCorrected: NoRepeat: No

13-187(c): the current inspection report shall be displayed in a conspicuous place; observed that the most recent inspection report was not on public view but is in the administration office

Jun 20, 2025

Permit/Opening

Score: 982 violations

30 - deck/rinse shower maintained

1 ptsCorrected: NoRepeat: No

13-201(b): if no bathhouse is required, a shower with tempered water shall be provided on the pool deck; no such shower exists at time of inspection

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-198(a): the equipment room shall be kept clean and organized with all chemical containers off direct contact with the ground

Jun 17, 2025

Permit/Opening

Score: 804 violations

3 - compliant drain covers secure, present and no cracks

15 ptsCorrected: NoRepeat: No

13-190(a)(4) - Main Drains must be covered by an approved secured grate observed: unable to verify grate compliance due to poor water clarity - imminent health hazard

4 - water clarity: main drains clearly visible

15 ptsCorrected: NoRepeat: No

13-189(c)(6) - Water clarity should be so clear that main drains are visible and the type, shape, and number of openings must be countable observed: water clarity was too opaque to view main drains - imminent health hazard

7 - ph between 7.2 and 7.8

15 ptsCorrected: NoRepeat: No

13-189)c)(1) - pool pH must be kept between 7.2 - 7.8. observed: pool pH was 6.6 imminent health hazard

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-190(a) - pools must have turnover rate that achieves required 6-hour turnover for the pool. observed: the flowmeter showed a flow rate of 70 gallons per minute (gpm), which is too low to achieve required turnover rate. Pool turnover must be 83 gpm or higher to achieve required turnover rate.

Jun 4, 2025

Permit/Opening

Score: 856 violations

5 - emergency phone operational and accessible

15 ptsCorrected: NoRepeat: No

13-202(g) An operable emergency telephone must be available with direct 911 access, directing emergency operators to the correct facility address observed: the 911 telephone operators did not have the correct address of the pool facility; operators said the facility address on file for the emergency phone was 785 Briarcliff Road, which did not match the pool facility's address.

8 - chemical feeder operational and approved

15 ptsCorrected: NoRepeat: No

13-197(a) pool water must be continuously treated with approved chemical disinfecting agents and associated approved chemical disinfectant equipment observed: the pool's chlorine feeder did not contain any chlorine tablets, and was thus, not operational.

21 - cyanuric acid level not exceeding maximum

4 ptsCorrected: NoRepeat: No

13-189(c)(2) - cyanuric acid levels should not exceed 100 ppm observed: Cyanuric acid levels were 91 ppm, which will exceed 100 ppm quickly if pool is opened and create an imminent health hazard. Draining the pool is recommended to bring cyanuric acid level down.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

2 ptsCorrected: NoRepeat: No

13-202(m) pools must post a minimum of 12 required rules conspicuously in the pool area observed: pf 12 required rules posted, the following were missing: "Bathers shall wear bathing attire" "An emergency telephone is located"

34 - inspection report placed in public view

1 ptsCorrected: NoRepeat: No

13-187(c)- the current inspection report must be posted conspicuously at all times observed: no current pool inspection was posted

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-202(n)- phone numbers of emergency numbers, pool operator, and health department must be posted by emergency phone observed: only 911 number was posted above emergency phone

Jul 9, 2024

Routine

Score: 932 violations

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

13-190(a)(7): A flow meter shall be installed to accurately indicate the circulation rate. Flow meter was inoperable.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

2 ptsCorrected: NoRepeat: No

13-202(m): Sign lettering shall be a minimum of 3/4 inches except as otherwise noted. "NO SOLO BATHING" and "CHILDREN MUST BE ACCOMPANIED BY AN ADULT" must be 2 inches. Those statements were not at least 2 inches high.

Jun 7, 2024

Permit/Opening

Score: 932 violations

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

13-190(a)(7): A flow meter shall be installed to accurately indicate the circulation rate. Flow meter was inoperable.

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

2 ptsCorrected: NoRepeat: No

13-202(m): Sign lettering shall be a minimum of 3/4 inches except as otherwise noted. "NO SOLO BATHING" and "CHILDREN MUST BE ACCOMPANIED BY AN ADULT" must be 2 inches. Those statements were not at least 2 inches high.

Aug 17, 2023

Permit/Opening

Score: 943 violations

36 - daily recordkeeping: water testing and self inspection performed

5 ptsCorrected: NoRepeat: No

13-189(c)(4) - pool water shall be tested for disinfectant and pH level at least two times each day. Observed no logbook showing pool is being tested at least twice daily

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-197(k) - storage rooms must have ventilation with one air change every 3 minutes exhausted to the exterior away from occupied areas. Observed broken exhaust fan

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-198(a) - equipment room shall be kept clean, safe and adequately lighted. Observed messy/cluttered equipment room. Advised to keep chemicals on shelves and to clean up equipment room

Jul 17, 2023

Permit/Opening

Score: 796 violations

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: No

13-189(c)(1): free-chlorine shall be maintained at a concentration of no less than 3ppm: I observed 1.70, CPO turned up chlorine then I observed 1.83, CPO turned up chlorine to the max and I got 2.03, waited 20 minutes and retested and got 2.01, CPO insisted that I retest and I observed 1.99pp,

8 - chemical feeder operational and approved

15 ptsCorrected: NoRepeat: No

13-197(a): the water in each pool shall be continuously chemically treated with approved disinfection agent, and equipment whereby the chlorine can be measured with a field test kit.; I observed the chemical feeder not operational as the free chlorine concentration did not increase and algae is starting to grow in the pool

11 - appropriate lifesaving equipment present

15 ptsCorrected: YesRepeat: No

13-202(d): each pool shall be provided with a lifesaving ring with a firmly attached throwing rope; I observed the throwing rope not attached to the lifesaving ring

36 - daily recordkeeping: water testing and self inspection performed

5 ptsCorrected: NoRepeat: No

13-202(c): each pool operator shall maintain and make available for inspection onsite upon request daily record keeping of operating information; I observed no log book available only an outside pool company test log

36 - daily recordkeeping: water testing and self inspection performed

5 ptsCorrected: NoRepeat: No

13-189(c)(4): the pool water shall be tested for disinfectant level and pH at least 2 times daily; I observed them not testing twice daily

34 - inspection report placed in public view

1 ptsCorrected: NoRepeat: No

13-187(c): the current inspection report shall be displayed in a conspicuous place so that it is easily readable by the public at all times upon entry into the pool area; I observed the current report not displayed

Jun 23, 2023

Permit/Opening

Score: 961 violation

21 - cyanuric acid level not exceeding maximum

4 ptsCorrected: NoRepeat: Yes

13-189(c): cyanuric acid levels shall not exceed 100ppm; I observed 99 for the cyanuric but retested because it was close to 100ppm and the CPO added chemicals to the pool to fix chlorine levels the second test was 106 ppm for cyanuric acid

Jun 5, 2023

Permit/Opening

Score: 736 violations

5 - emergency phone operational and accessible

15 ptsCorrected: NoRepeat: No

13-202(g): an operable, hard-wired, weatherproof telephone, with 911 access; i observed the phone not working

6 - proper disinfectant level

15 ptsCorrected: NoRepeat: No

13-189(c)(1) Free Chlorine must stay between 3-10 ppm. Observed at 12.13+

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

13-190(a)(7): an adequately sized flow meter shall be installed on the return line to accurately indicate the circulation rate in gallons per minute (GPM); I observed the flow meter not indicating the circulation rate

21 - cyanuric acid level not exceeding maximum

4 ptsCorrected: NoRepeat: No

13-189(c): cyanuric acid levels shall not exceed 100ppm; I observed 115

12 - grab/hand rails, ladders installed and secure

2 ptsCorrected: NoRepeat: No

13-188(f): all steps shall have handrails anchored in the bottom step; I observed two handrails missing

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-202(i): a written copy of the emergency action plan shall be located to allow for immediate access in case of an emergency

13-187(c): the operating permit shall be framed and displayed in a conspicuous place near the pool entrance