North Druid Hills, DeKalb County

BRISTOL AT BRIARCLIFF CONDOMINIUMS

2660 ALMHOUSE LN ATLANTA, GA 30329

Pool
Latest score
79
Jun 11, 2026
City
North Druid Hills
County
DeKalb
Inspections
7

Score history

Inspection scores over time for this facility.

Inspection history

Georgia inspection history is score-based, with violations grouped under each recorded inspection.

Jun 11, 2026

Permit/Opening

Score: 793 violations

5 - emergency phone operational and accessible

15 ptsCorrected: NoRepeat: No

15-202(g): An operable, hard wired phone with direct 911 access must be accessible at all times. Observed emergency phone not operational.

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-205(b)(1): Pool equipment shall be operated 24 hours a day such that pool water is completely turned over once every 6 hours. Observed 2 flowmeters at 70 GPM; required flow rate is 152 GPM.

34 - inspection report placed in public view

1 ptsCorrected: NoRepeat: No

13-187(c): The current inspection report shall be displayed in a conspicuous manner. Observed no inspection report on site and no place to display inspection report.

Jul 17, 2025

Permit/Opening

Score: 952 violations

15 - depth and no diving markers, step marking; installed and contrasting

4 ptsCorrected: NoRepeat: No

13-188(d)(1) - Permanent non-slip tile depth markers, with dark text on a white background, and with lettering and numbering at least 4 inches in size must be installed in the pool and pool deck. observed: Depth markers listed pool depth in feet and "1/2" feet. Recommended to CPO to replace as soon as possible.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-198(b) - Pump rooms must have adequate ventilation supplemented by an exhaust fan capable of creating 1 full enclosure air exchange every 3 minutes. Observed no exhaust fan in pump room. Exhaust fan must be installed to create ventilation.

Jul 15, 2025

Permit/Opening

Score: 745 violations

2 - self-closing / self-latching gates

15 ptsCorrected: NoRepeat: No

13-202(a)(2) - Pools shall have gates that self-latch and close automatically after being swung open. Observed pool entrance gate magnet latch not operational. imminent health hazard. Gate to pump room must also remain closed and locked at all times.

19 - adequate turnover rate

5 ptsCorrected: NoRepeat: No

13-190(a) - Pool equipment shall be operated 24 hours a day such that pool water is completely turnover at least 4 times a day. Observed: Flow rate for this 55000-gallon pool should be above 152 gpm. Flowrate observed at 115 gpm. spoke to CPO about servicing pumps soon.

15 - depth and no diving markers, step marking; installed and contrasting

4 ptsCorrected: NoRepeat: No

13-188(d)(1) - Permanent non-slip tile depth markers, with dark text on a white background, and with lettering and numbering at least 4 inches in size must be installed in the pool and pool deck. observed: Depth markers listed pool depth in "1/2" feet. Recommended to CPO to replace as soon as possible.

34 - inspection report placed in public view

1 ptsCorrected: NoRepeat: No

13-187(c)- The current inspection report shall be displayed in a conspicuous manner. Observed no inspection report posted.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-202(i) - Each pool facility must have an emergency action plan posted on site with all sections filled out. observed: No emergency action plan present at pool facility. Left template with CPO. imminent health hazard.

Apr 25, 2024

Permit/Opening

Score: 912 violations

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

13-190(a)(7) An adequately sized flow meter shall be installed on the return line to accurately indicate the circulation rate in gallons per minute (GPM), shall be conspicuously located. Observed flow meter sized too small for an accurate flow rate reading for pool.

15 - depth and no diving markers, step marking; installed and contrasting

4 ptsCorrected: NoRepeat: No

13-188(d)(1) Permanent, slip-resistant, easily-readable depth markers at least 4 inches (4") high; black letters and numbers on a white background indicated in feet and inches when applicable (metric allowed only if accompanied by feet and inches. Observed depth markers reading in 1/2 markers.

Jul 26, 2023

Re-inspection

Score: 788 violations

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: Yes

13-190(a)(7): an adequately sized flow meter shall be installed on the return line to accurately indicate circulation rate in gallons per minute (GPM); I observed both flow meters having the wrong range, the max range on the flow meter should be about 315 gpm to indicate the correct circulation rate of 208 gpm for this 75000 gallon pool

36 - daily recordkeeping: water testing and self inspection performed

5 ptsCorrected: NoRepeat: No

13-202(c)(4): the pool water shall be tested for disinfectant level and pH at least 2 times a day; I observed the daily record-keeping (log book) book blank

15 - depth and no diving markers, step marking; installed and contrasting

4 ptsCorrected: NoRepeat: Yes

13-188(d)(1): black letters and numbers on a white background indicated in feet and inches; I observed only in feet e.g. 3 1/2 and 8 1/2 feet

32 - operator training certification available onsite and approved

4 ptsCorrected: NoRepeat: Yes

13-187(c): a copy of the pool operator's certificate shall be conspicuously displayed near operating permit; I observed the CPO certification not displayed

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

2 ptsCorrected: YesRepeat: No

13-202(m); safety rules and regulations shall be easily readable and shall be conspicuously displayed; I observed statements "bather load" and "hours of operation" not being filled out on the sign

29 - toilets & lavatories: clean, maintained, and stocked

1 ptsCorrected: YesRepeat: Yes

13-184(e)(5): imminent health hazards exist if the sanitary facility are not maintained in a clean and sanitary condition; I observed the shower in the men's sanitary facility not being clean

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: Yes

13-202(i): a written copy of the emergency action plan (EAP) shall be located to allow for immediate access in case of an emergency; I observed the EAP in the pump room and not in the pool area

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: Yes

13-187(c): the operating permit shall be framed and displayed as close as the pool entrance so that it is easily readable by the public; I observed no permit displayed

Jul 25, 2023

Routine

Score: 6112 violations

7 - ph between 7.2 and 7.8

15 ptsCorrected: NoRepeat: No

13-189(c)(1): the pool shall be maintained in an alkaline condition at all times with a pH level between 7.2 to 7.8; I observed 6.9

28 - flow meter: appropriate range and location

5 ptsCorrected: NoRepeat: No

13-190(a)(7): an adequately sized flow meter shall be installed on the return line to accurately indicate circulation rate in gallons per minute; I observed the flow meter not having an adequate enough size to indicate circulation rate accurately

15 - depth and no diving markers, step marking; installed and contrasting

4 ptsCorrected: NoRepeat: Yes

13-188(d)(1): black letters and numbers on a white background indicated in feet and inches; I observed only in feet e.g. 3 1/2 and 8 1/2 feet

17 - skimmers/gutters maintained and operable

4 ptsCorrected: NoRepeat: No

13-186(a)(4): each skimmer shall have a properly designed and operating weir; I observed no weirs in the skimmers

32 - operator training certification available onsite and approved

4 ptsCorrected: NoRepeat: Yes

13-187(c): a copy of the pool operator's certificate shall be conspicuously displayed near operating permit; I observed the CPO certification not displayed

16 - pool deck: maintained, unobstructed and clean

2 ptsCorrected: NoRepeat: No

13-188(h)(4): decks shall not retain any standing water greater that 1/8" in depth or greater than 1sqft of area. Adjacent areas to the deck and walkways within the pool enclosure shall be safe and well drained; I observed the water past the water line tiles and water coming out of the skimmers covers on the pool deck

22 - signs: peak occupancy/pool/spa/signs legible and in clearview

2 ptsCorrected: NoRepeat: No

13-202(m): rules must contain at a minimum the 12 statements in the pool code; I observed statements "bather load" and "hours of operation" not being filled out on the sign

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-202(i): a written copy of the emergency action plan (EAP) shall be located to allow for immediate access in case of an emergency; I observed no EAP available

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-187(c): the operating permit shall be framed and displayed in a conspicuous place as close as the pool entrance as possible such that it is easily readable by the public at all times; I observed the operating permit not being displayed

29 - toilets & lavatories: clean, maintained, and stocked

1 ptsCorrected: NoRepeat: No

13-201(k): at all times an adequate supply of liquid soap, toilet paper, and paper towels shall be provided and stored; I observed no paper towels in either of the men and women's sanitary facilities

29 - toilets & lavatories: clean, maintained, and stocked

1 ptsCorrected: NoRepeat: No

13-184(e)(5): imminent health hazard exist if sanitary facilities are not functional or not maintained in a clean and sanitary condition; I observed the overhead light not working in the women's sanitary facility and the the shower in the men's sanitary facility was not clean

34 - inspection report placed in public view

1 ptsCorrected: NoRepeat: Yes

13-187(c): the current inspection report shall be displayed in a conspicuous place where it is easily readable by the public at all times upon entry to the pool area; I observed the current inspection report (the last routine inspection) not displayed

Jun 7, 2023

Routine

Score: 906 violations

15 - depth and no diving markers, step marking; installed and contrasting

4 ptsCorrected: NoRepeat: No

13-188(d)(1): black letters and numbers on a white background indicated in feet and inches; I observed only in feet e.g. 3 1/2 feet

32 - operator training certification available onsite and approved

4 ptsCorrected: NoRepeat: No

13-187(c): a copy of the pool operator's certificate shall be conspicuously displayed near operating permit

34 - inspection report placed in public view

1 ptsCorrected: NoRepeat: No

13-187(c): the current inspection report shall be displayed in a conspicuous place where it is easily readable by the public at all times upon entry to the pool area

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-188(a): pool surfaces shall have no cracks; I observed cracks on the pool floor near the deep en/ main drain.

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-202(i): a written copy of the emergency action plan shall be located in the pool area to allow for immediate access

37 - other violations of the chapter

1 ptsCorrected: NoRepeat: No

13-187(c): the operating permit shall be framed and displayed in a conspicuous place as close as the pool's entrance