Aug 26, 2025
Permit/Opening
29 - toilets & lavatories: clean, maintained, and stocked
13-201(k): Observed both men's and women's restrooms without hand soap and body soap. CA: At all times, an adequate supply of liquid soap, toilet paper and paper towels shall be provided and stored in appropriate dispensers conveniently accessible to users. A minimum of 1 diaper changing station for babies shall be provided in each men’s and women’s section of the bathhouse. (Bar soap shall not be provided to bathers)
37 - other violations of the chapter
13-198(b): Observed exhaust fan in equipment inoperable upon inspection. Property manager stated that they are in the process of repairing the exhaust fan in the equipment room. CA: Ready access, suitable drainage (such as a sump pump) and ventilation of fresh make-up air must be provided for all equipment rooms. The enclosure must be ventilated with outside air by a chlorine-resistant exhaust fan with vents that are located a maximum of four inches (4”) above the floor level, equipped with automatic louvers to achieve cross-flow ventilation located at the top of the enclosure for admitting fresh air, and capable of providing one (1) enclosure air change every three (3) minutes. The exhaust fan shall be installed so as to exhaust the equipment room air away from the pool enclosure and adjacent inhabited areas. The entire enclosure shall have a concrete floor that slopes one-quarter inch per foot (¼” / 1’) to a floor drain connected to a sanitary sewer. A hose bibb with an approved backflow prevention system shall be provided in the equipment room or enclosure.